232/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
A3
#
SA
Oil actuator has detected own fault and
reported it to the basic unit.
Type of fault: See diagnostic code
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
A3
See A1
See A1
See A1
See A1
See A1
A4
#
SA
Auxiliary actuator 1 has detected own
fault and reported it to the basic unit.
Type of fault: See diagnostic code
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
A4
See A1
See A1
See A1
See A1
See A1
A5
#
SA
Auxiliary actuator 2 has detected own
fault and reported it to the basic unit.
Type of fault: See diagnostic code
Check CAN cabling and terminators as specified
If fault occurs sporadically: Improve EMC
If fault occurs constantly: Replace defective actuator
A5
See A1
See A1
See A1
See A1
See A1
A6
#
LC
Internal load controller has detected own
fault and reported it to the basic unit.
Type of fault: See diagnostic code
A6
10
LC
No actual Value Slope at End of
Identification
*1)
A6
12
LC
Adaption invalid
Invalid XP identified
*1)
A6
13
LC
Adaption invalid
Invalid TN identified
*1)
A6
14
LC
Adaption invalid
TU longer than identification time
*1)
A6
15
LC
Adaption invalid
Invalid TN identified
*1)
A6
16
LC
Timeout with Adaption
Timeout during observation time
*1)