Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Description
Value range
Access
rights
Default pa-
rameter
setting
LMV51 LMV52
138/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
7 Display and operating unit AZL5...
13.08.2004
D-Part (Tv)
Controller parameter differential part
0..1000 s
User
40 s
x
x
MinActuatorStep
Minimum actuator step possible
0.5..10 %
User
1 %
x
x
SW_FilterTmeCo
n
Software filter time constant
1..10 s
User
3 s
x
x
SetpointW1
Internal setpoint W1, in °C
Internal setpoint W1, in bar
0..2000 °C
0..100 bar
User
---
x
x
SetpointW2
Internal setpoint W2, in °C
Internal setpoint W2, in bar
0..2000 °C
0..100 bar
User
---
x
x
SD_ModOn
2-position controller switching differential burner ON modulat-
ing referred to the current setpoint (Wcurrent)
-50..+50 % Wcurrent
User
1.0 %
x
x
SD_ModOff
2-position controller switching differential burner OFF modulat-
ing referred to the current setpoint (Wcurrent)
0..+50 % Wcurrent
User
10 %
x
x
SD_Stage1On
2-position controller switching differential burner ON multistage
referred to the current setpoint (Wcurrent)
-50..+50 % Wcurrent
User
-2 %
x
x
SD_Stage1Off
2-position controller switching differential stage 1 OFF referred
to the current setpoint (Wcurrent)
0..+50 % Wcurrent
User
10 %
x
x
SD_Stage2Off
2-position controller switching differential stage 2 OFF referred
to the current setpoint (Wcurrent)
0..+50 % Wcurrent
User
8 %
x
x
SD_Stage3Off
2-position controller switching differential stage 3_1 OFF re-
ferred to the current setpoint (Wcurrent)
0..+50 % Wcurrent
User
6 %
x
x
ThreshStage2On
Reaction threshold Q2 for switching on stage 2
(integral control deviation * time)
0..1000
User
300
x
x
ThreshStage3On
Reaction threshold Q3 for switching on stage 3
(integral control deviation * time)
0..1000
User
600
x
x
TempLimiter
Settings for the temperature limiter function
Service x
x
TL_ThreshOff
Temperature limiter OFF threshold, in °C
0..2000 °C
Service
95 °C
x
x
TL_SD_On
Temperature limiter switching differential ON
-50..0 % TL_Thresh_Off
Service
-5 %
x
x
ColdStart
Settings for the cold start (thermal shock protection)
Service x
x
ColdStartOn
Cold start thermal shock protection, activate / deactivate
deactivated
activated
Service deactivated
x
x
ThresholdOn
Cold start thermal shock protection activation level referred to
the current setpoint (Wcurrent)
0..100 % Wcurrent
Service
20 %
x
x
StageLoad
Cold start thermal shock protection load step (modulating)
0..100 %
Service
15 %
x
x
StageSetp_Mod
Cold start thermal shock protection setpoint step (modulating)
referred to the current setpoint (Wcurrent)
1..100 % Wcurrent
Service
5 %
x
x
Stage-
Cold start thermal shock protection setpoint step (multistage)
1..100 % Wcurrent
Service
5 %
x
x