Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Description
Value range
Access
rights
Default pa-
rameter
setting
LMV51 LMV52
140/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
7 Display and operating unit AZL5...
13.08.2004
MRange Temp-
Sens
End of temperature measuring range for input X61
0..2000 °C
Service
90 °C
x
x
MRange Press-
Sens
End of pressure measuring range for input X61
0..99.9 bar
Service
2 bar
x
x
Ext Inp X62 U/I
Configuration of external input X62
4..20 mA
0 / 2..10 V
Service
4..20 mA
x
x
Ext MinSetpoint
Accepted preselected minimum external setpoint for X62 / bus 0..100 % ScaleHIcurrent
Service
0 %
x
x
Ext MaxSetpoint
Accepted preselected maximum external setpoint for X62 / bus 0..100 % ScaleHIcurrent
Service
60 %
x
x
Adaption
Adapting the controlled system
User x
x
StartAdaption
User x
x
AdaptionLoad
Adaption load
40..100 %
User
100 %
x
x
SW Version
SW version of internal load controller
0..65535
User
---
x
x
AZL
Settings for the display and operating unit
User x
x
Times
AZL5...-specific time settings
User x
x
PasswordTime
Validity of password
10..480 min
OEM
120 min
x
x
Sum/WinterTime
Setting the summer-/wintertime
Manual
Automatic
User
Automatic
x
x
Time EU/US
Setting the summer-/wintertime US / EU
S / W time EU
S / W time US
User
S / W time
EU
x
x
Language
Selection of language
English
German
Language 3
Language 4
Language 5
Language 6
User
German
x
x
DateFormat
Selection of date format (Day.Month.Year or Month-Day-Year)
DD.MM.YY
MM-DD-YY
User
DD.MM.YY
x
x
PhysicalUnits
User
x
x
UnitTemperature
Selection of display format °C or F
Display °C
Display °F
User
Display °C
x
x
UnitPressure
Selection of display format bar or psi
Display bar
Display psi
User
Display bar
x
x
eBUS
User
x
x
Address
E-bus address of LMV5...
1..8
User
1
x
x
SendCycleBU
Cycle time for sending the burner control's operating data to
BAS
10..60 s
User
30 s
x
x