
Representation of parameters based on the AZL5... menu structure, «OEM» level, as supplied by Siemens
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Description
Value range
Access
rights
Default pa-
rameter
setting
LMV51 LMV52
137/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
7 Display and operating unit AZL5...
13.08.2004
A2
Adjustable constant for calculating the combustion efficiency
(oil)
0.40..0.80
Service
0.65 x
B / 1000
Adjustable constant for calculating the combustion efficiency
(oil)
1..20
Service
9
x
O2 Content Air
Oxygen content of air
0..30 %
OEM
20.9 %
x
Type Air Change
Impact of air density change on O2 value
like theory
like P air
OEM
like theory
x
O2 OffsetOil
O2 offset during change of load oil
0...5 %
Service
0 %
x
LoadCtrlSus-
pend
Difference between delayed and current load
0...25 %
Service
5 %
x
FilterTimeLoad
Filter time for delayed load
4...10
Service
5
x
Process Data
User
x
CombEfficiency
Combustion efficiency
0..200 %
User
---
x
ManVar O2 Ctrl
Manipulated variable of O2 trim controller
-35..35 %
User
---
x
State O2 Ctrl
Release O2 trim controller
deactivated
locked
LockTStaff
InitContr
LockTLoad
active
LockTCAct
User
---
x
Air-related Load
0..100%, S1, S2, S3
User
---
x
Diag Reg State
Diagnostic code when controller is locked
0...255
User
---
x
LoadController
Settings for the internal load controller
User x
x
Controller-
Param
Setting the controller parameters
User x
x
ContrlParam-
List
PID control parameters
User x
x
StandardParam
Selection of standard parameter sets for the load controller
Adaption
very fast
fast
normal
slow
very slow
User
---
x
x
P-Part (Xp)
Controller parameter proportional band
2..500 %
User
15 %
x
x
I-Part (Tn)
Controller parameter integral part
0..2000 s
User
320 s
x
x