155/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
8 Commissioning instructions for the LMV5... system
13.08.2004
The burner control stops startup during the prepurge phase (Phase 24).
The positions of the actuators for prepurging can thus be set very straightforwardly.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
RatioControl
GasSettings
SpecialPositions
PrepurgePos
PrepurgePosAir
PrepurgePosAux
PrepurgeAux2
PrepurgeAux3
PrepurgeVSD
Only
LMV52...
The prepurge position of auxiliary actuator 3 is approached in Phase 32 (FGR).
After the settings have been made, the program stop in the prepurge position should be
replaced by the program stop of the ignition position in Phase 36.
The burner control continues the startup sequence until the ignition position (Phase 36)
is reached. Then, it stops again so that the actuator’s ignition positions can be set.
Menu level 1
Menu level
2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
RatioControl
GasSettings
SpecialPositions
IgnitionPos
IgnitionPosGas
IgnitionPosAir
IgnitionPosAux
Aux2
Aux3
VSD
Only
LMV52...
To verify the ignition positions again, the program sequence can be stopped in interval
phase 44 or 52 (interval with ignited flame on completion of the relevant safety time).
On deactivation of the program stop, the burner continues its program until the operat-
ing phase (Phase 60) is reached.
If no point for the fuel / air ratio control system has as yet been predefined, the first
curvepoint «P1» to be adopted on a preliminary basis are the ignition positions of the
actuators.
13. Actuator positions
during the prepurge time
Note:
14. Ignition positions