241/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
A9
#
VSD module Fault VSD Module
VSD module has detected own fault and
reported it to the basic unit.
Type of fault: See diagnostic code
A9 01
VSD
module Internal Fault VSD Module
CRC fault during ROM test
*1)
A9 02
VSD
module Internal Fault VSD Module
CRC fault during RAM test
*1)
A9 04
VSD
module Internal Fault VSD Module
Fault during key value check
*1)
A9 05
VSD
module Internal Fault VSD Module
Error code for time block overflow
*1)
A9 07
VSD
module Internal Fault VSD Module
Sync fault or CRC fault
*1)
A9 08
VSD
module Internal Fault VSD Module
Error code for main loop counter
*1)
A9 09
VSD
module Internal Fault VSD Module
Fault during stack test
*1)
A9 0A
VSD
module Internal Fault VSD Module
Max IRQ speed reached
Possibly interference on the line to the speed sensor, check
cable routing, use shielding
*1)
A9 0C
VSD
module Alarm from VSD
VSD reports a fault to the VSD module
Fault has been triggered by the VSD.
Read VSDs error code.
Check VSD settings (ramps, motor settings), increase ramp
time on VSD and basic unit, if necessary.
Check combination VSD / motor size
A9 0D
VSD
module Control Range Limitation VSD
Module
VSD module could not offset speed differ-
ential within its control limits
Check to see if the current interfaces of VSD and VSD
module use the same setting (0/4...20 mA).
Standardize the speed.
!! Note !!
After standardizing the speed -> check setting of combus-
tion mixture !
A9 0E
VSD
module Internal Fault VSD Module
Fault during the speed calculation test
*1)
A9 15
VSD
module Internal Fault VSD Module
CAN bus fault, disturbed CAN bus trans-
missions
If fault occurs sporadically: Check CAN bus wiring.
Improve EMC.
Check terminating resistors and correct, if necessary