166/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
8 Commissioning instructions for the LMV5... system
13.08.2004
8.1.6 Control parameters of the load controller
The control parameters can be defined in 3 different ways.
The memory of the load controller contains 5 standard parameter sets.
Depending on the characteristics of the controlled system, a PID triple value can be se-
lected and activated.
The following standard parameter sets can be chosen:
P [%]
I [s]
D [s]
Very fast
40
55
15
Fast
4
35
17
Normal
7
90
50
Slow
15
320
40
Very slow
30
400
10
Alternatively, the PID parameters can be directly selected and set within the predefined
value range.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
LoadController
ControllerParam
ContrlParamList
StandardParam
Adaption
very fast
fast
normal
slow
very slow
Or
P-Part (Xp)
I_Part (Tn)
D-Part (Tv)
With the method of adapting the control parameters, the characteristic data of the con-
trolled system are acquired with an adaption procedure whereupon matching PID pa-
rameters will be calculated.
If possible, the adaption load should be 100 %.
Menu level 1
Menu level 2
Menu level 3
Menu level 4
Menu level 5
Menu level 6
Params & Display
LoadController
Adaption
StartAdaption
AdaptionLoad
1. Selection of the
standard parameter set
2. Individual setting of
the PID parameters
3. Automatic adaption