7 Basic unit LMV27
17.12.2018
Oil pressure switch-max
In all types of oil trains, the maximum oil pressure is monitored from phase 22. If the
maximum oil pressure is exceeded after the maximum time (parameter 214) has
elapsed, or during the subsequent phases, the system initiates lockout.
No. Parameter
214
Maximum time to start release
Error
code
Diagnostic
code
Meaning for the LMV27
14 0
POC
open
1 POC
close
21
0
Pressure switch-max: Maximum oil pressure exceeded
POC: POC open (software version
V02.00)
1
POC close (software version
≤
V02.00)
During the safety times, the signal from pressure switch-max is only assessed after a
certain period of time has elapsed in order to ignore the pressure shocks that occur the
moment the valves open.
No. Parameter
269
Oil: Time to respond to pressure faults in the first and second safety time
The pressure switch connection can also be used as POC (Proof of Closure) (refer to
chapter
Sequence diagrams
).
No. Parameter
277
Oil: Input pressure switch-max / POC
1 = pressure switch-max
2 = POC
3 = not used
4 = additional speed-dependent air pressure switch
Note
If the input is used for POC, pressure switch-max can be included in the safety loop.
In that case, pressure switch-max must not be installed between the valves, but
always downstream from them.
Start release oil
If the input is simultaneously used as a start release input, e.g. for an air supply damper,
the latter can be connected in series with the pressure switch.
Whit parameterization with POC function cannot be used as start release input.
7.3.10
Reset X8-04, pin 1
Input for connection of a reset button. The LMV27 can be reset or manually locked via
this input (refer to chapter
Reset/manual locking
).
Resetting / manual interlocking
Bild 393e/1109
Figure 21: Reset X8-04