180/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
26 Parameter level
17.12.2018
26.11.13 Intensity of flame during curve settings
When setting the curve and the curvepoint is displayed, you can press
/reset
to show the intensity of flame.
When pressing the button for >1 s, a change to parameter 954 is made; when releasing the button, you
return to the curvepoint.
P
V
h min s
%
Bi
ld
123
/0
707
Example: Curvepoint
Low-flame position
P1.
/reset
>1 s
Change to parameter
954
Parameter
954:
flashes.
The intensity of flame in % is shown on the right.
Example:
954: 0.0
/reset
P
V
h min s
%
Bi
ld
123
/0
707
Release
/reset
to return to curvepoint
Low-fire
position
P1.