206/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
28 Error code list (of all LMV2 / LMV3 types)
17.12.2018
Error
code
Diagnostic code
Meaning for the LMV27
Recommended measures or causes
124
#
Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the LMV27
125
#
Internal error EEPROM read access
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV27
126
#
Internal error EEPROM write access
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV27
127
#
Internal error EEPROM access
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the LMV27
128
0
Internal error EEPROM access - synchronization during
initialization
Make a reset; if error occurs repeatedly, replace the LMV27
129 #
Internal error EEPROM access – command
synchronization
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV27
130
#
Internal error EEPROM access - timeout
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV27
131
#
Internal error EEPROM access - page on abort
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV27
132
#
Internal error EEPROM register initialization
Make a reset; if error occurs repeatedly, replace the LMV27
133
#
Internal error EEPROM access – Request synchronization
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV27
134
#
Internal error EEPROM access – Request synchronization
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV27
135
#
Internal error EEPROM access – Request synchronization
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the LMV27
136 #
Restore
1 Restore
started
Restore of a backup has been started (no error)
New LMV27 require resetting following restore!
for further diagnostic codes for error code 136, refer to
error code 137
For measures, refer to error code 137
137
#
Internal error – backup / restore
157 (-99)
Restore – ok, but backup < data set of current LMV27
Restore successful, but backup data set is smaller than in the current LMV27
239 (-17)
Backup – storage of backup in AZL2 faulty
Make reset and repeat backup
240 (-16)
Restore – no backup in AZL2
No backup in AZL2
241 (-15)
Restore – abortion due to unsuitable product no. (ASN)
Backup has an unsuitable product no. (ASN) and must not be loaded on the LMV27
242 (-14)
Backup – backup made is inconsistent
Backup is faulty and cannot be transferred back
243 (-13)
Backup – data comparison between µCs faulty
Reset and repeat backup
244 (-12)
Backup data are incompatible
Backup data are incompatible with the current software version, restore not possible
245 (-11)
Access error to parameter Restore_Complete
Repeat reset and backup
246 (-10)
Restore – timeout when storing in EEPROM
Repeat reset and backup
247 (-9)
Data received are inconsistent
Backup data set invalid, restore not possible
248 (-8)
Restore cannot at present be made
Repeat reset and backup
249 (-7)
Restore – abortion due to unsuitable burner identification
Backup has an unsuitable burner identification and must not be transferred to the LMV27
250 (-6)
Backup – CRC of one page is not correct
Backup data set invalid, restore not possible