166/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
26 Parameter level
17.12.2018
Air
Fuel
Curvepoints
An
g
le
B
ild
216e
/1
10
9
Figure 82: Setting the curvepoints
Note
Curvepoints
P2
to
P8
are automatically calculated as a straight line between
P1
and
P9
.
Example 1 = gas modulating
P0
,
P1
and
P9
are set as described:
Curvepoint
Value 1
fuel
Value 2
air
P0
30.0
22.0
P1
32.0
24.0
P9
80.0
90.0
P2
through
P8
have automatically been
calculated:
Curvepoint
Value 1
fuel
Value 2
air
P2
38.0
32.3
P3
44.0
40.5
P4
50.0
48.8
P5
56.0
57
P6
62.0
65.3
P7
68.0
73.5
P8
74.0
81.8