28 Error code list (of all LMV2 / LMV3 types)
17.12.2018
Error
code
Diagnostic code
Meaning for the LMV27
Recommended measures or causes
incorrectly.
0
Trim function at lower limit
1
Trim function at upper limit
10
Fuel 1: Trim function at lower limit
11
Fuel 1: Trim function at upper limit
157
#
Trim function: Analog input test
Test value of the analog input is outside the tolerance range
0
Analog value standby
1. Check whether a current setting of 12 mA is present in standby.
2. Check parameter 916 (permissible value range -1...+1%).
1
Analog value prepurging
1. Check whether a current setting of 4 mA is present in prepurging.
2. Check parameter 916 (permissible value range -16...-14%).
165 #
Internal
error
166
0
Internal error watchdog reset
167 #
Manual
locking
LMV27 has been manually locked (no error)
1
Manual locking by contact
2
Manual locking by AZL2
3
Manual locking by ACS410 PC software
8
Manual locking by the AZL2
Timeout / communication breakdown
During a curve setting via the AZL2, the timeout for menu operation has elapsed (setting via
parameter 127), or communication between the LMV27 and the AZL2 has broken down
9
Manual locking by the ACS410
PC software
Communication breakdown
During a curve setting via the ACS410, communication between the LMV27 and the ACS410 was
interrupted for more than 30 seconds
33
Manual locking after ACS410
PC software
reset attempt
ACS410
PC software made a reset attempt although the system worked correctly
168
#
Internal error management
Make a reset; if error occurs repeatedly, replace the LMV27
169
#
Internal error management
Make a reset; if error occurs repeatedly, replace the LMV27
170
#
Internal error management
Make a reset; if error occurs repeatedly, replace the LMV27
171
#
Internal error management
Make a reset; if error occurs repeatedly, replace the LMV27
200
OFF
# LMV27
error-free
No error
201
OFF
UPr
# Start
prevention
Start prevention due to unparameterized LMV27
Go to error history, entry 702, for initial cause of the error with shutdown in connection with the
first curve settings
Bit 0
Valency 1
No operating mode selected
Bit 1
Valency 2..3
No fuel train defined
Bit 2
Valency 4..7
No curves defined