167/219
Building Technologies
Basic Documentation LMV27...
CC1P7541en
26 Parameter level
17.12.2018
Continue the same way with P2 through P9!
F
or
A
and
or
P
V
h min s
%
Bi
ld
125
/0
707
High-fire position
P9
can only be set when
symbol
or
is no longer highlighted.
If required, readjust the gas pressure.
For fuel, keep
F
depressed, for air
A
.
Press
or
to adjust the value.
When symbol
or
is no longer
highlighted, the next curvepoint
P8
can be
selected with
.
After setting the high-fire point (P9), either a change to parameter 546 (automatic operation) can be
made (ESC) or all curvepoints can be run through in the reverse order.
If the gas pressure is changed, all curvepoints must be checked and – if required – readjusted.
ESC
P
V
h min s
%
Bi
ld
126
/0
707
The maximum capacity is displayed.
If the display shows
- - - -
, the maximum
capacity has not yet been specified.
The LMV27 can be run up to 100%.
You can press
/reset
to go to editing mode,
enabling you to change the maximum capacity.
To the next parameter
P
V
h min s
%
Bi
ld
127
/0
707
The minimum capacity is displayed.
If the display shows
- - - -
, the minimum
capacity has not yet been entered.
The LMV27 can be run down to 20%.
You can press
/reset
to go to editing mode,
enabling you to change the minimum capacity.
ESC
Completing
parameterization of the
curve
Back to the previous
parameter.