
BA 5060 EN 04/2011
10.
Maintenance and repair
Observe the instructions in section 3, "Safety instructions", and in section 9, "Faults, causes and remedy"!
10.1
General notes on maintenance
All maintenance and repair work must be done with care and by duly trained and qualified personnel only.
The following applies to all work in item 10.2:
Switch the gear unit and addon components off.
Secure the drive unit to prevent it from being started up unintentionally.
Attach a warning notice to the start switch.
The periods indicated in table 13 largely depend on the conditions under which the
gear unit is operated. Only average periods can therefore be stated here. These refer
to:
a daily operating time of
24 h
a duty factor "ED" of
100 %
an inputdrive speed of
1500 1/min
an operating temperature of
80 °C (applies to mineral oil)
The operator must ensure that the intervals stated in table 13 are adhered to.
This also applies if the maintenance work is included in the operator’s internal
maintenance schedules.
Table 13:
Maintenance and repair work
Measures
Periods
Remarks
Check the oil temperature
Daily
Check for unusual gear-unit noise
Daily
Check the oil level
Monthly
– Middle of the oil-sight
glass
and/or
– Upper mark on the
oil dipstick
Comparison of vibration values for
bearing monitoring with initial values
(reference values) on starting up
Every 3000 operating hours
See item 7.2.5.
The proper function and
measurement accuracy of the
ignition-protection system for the
temperature monitoring should be
checked at regular intervals
according to the instructions of the
manufacturer of the
ignition-protection device
See instructions of the manufacturer
The operator must ensure
this!
Check gear unit for leaks
Monthly
Test the oil for water content
After approx. 400 operating hours,
at least once per year
See item 10.2.1.
Perform the first oil change
Approx. 400 operating hours
after start-up
See item 10.2.2.
Perform subsequent oil changes
Every 4 years or after
max. 20 000 operating hours
See item 10.2.2.