6-Channel F Analog Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
94
A5E00482820-12
9.8
Technical Specifications
Technical Specifications for 6-Channel F Analog Input MTA
(6ES7650-1AH51-5XX0 or 6ES7650-1AH50-5XX0)
Dimensions - See Section 1, Figure 1.3, Long Version
Mounting
DIN Rail
35mm (deep top hat style)
Power Input
Voltage Input for Single or Redundant Feed
21.6 to 28.8 VDC
Current Consumption (nominal ratings; all
channels connected)
Inrush
9.368 A maximum (Includes 9.000 A for
transmitter inrush)
Normal
0.5 A maximum
Terminal Block Wire Sizes
TB100 & TB101
Wire Size – US
24 – 14 gauge AWG
Wire Size – Metric
0,205 – 2,08 mm sq.
Power Supply Specifications
See Module Specs
Fuse Ratings
Individual channel
1.5 A Fast blow (Littelfuse P/N: 273 01.5)
(Siemens Spare P/N: A5E01568886)
Module Power
0.5 A (Bussmann P/N: GMA-0.5A)
(Siemens Spare P/N: A5E01568885)
Indicators
Input Power
Green LED on when input power available
Module Power
Green LED on when module power available
Channel Power
Green LED on when sensor power available
Field Terminal Block Wire Sizes TB1 – TB3
Wire Size – US
24 – 14 gauge AWG
Wire Size – Metric
0,205 – 2,08 mm sq.
Environmental
Ambient Temperature
-25C to +60C
Humidity
5% to 95% Non-condensing
Approvals
MTA Agency Approvals
See Preface section, Approvals Table
Max achievable Safety Integrity Level in safety mode
In Accordance with IEC 61508
SIL 3
Fail-safe performance characteristics
Low demand mode (average probability of failure
on demand) per channel
PFDavg <1E-4 @60C
High demand / continuous mode ( probability of a
dangerous failure per hour per channel)
PFH < 1E-9
Proof-test interval
20 years
Содержание ET 200M
Страница 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Страница 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Страница 26: ......
Страница 78: ...8 Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 78 A5E00482820 12 ...
Страница 136: ......
Страница 154: ...6 Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 154 A5E00482820 12 ...
Страница 166: ......
Страница 196: ......
Страница 236: ......
Страница 252: ......
Страница 270: ...8 Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 270 A5E00482820 12 ...
Страница 278: ......
Страница 284: ...Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I O Modules 284 A5E00482820 12 ...