8-Channel RTD Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
74
A5E00482820-12
7.9
Typical R & RTD Connection to Field Terminals
Note
•
When connecting an RTD in 2-wire Mode there will be no resistance error
correction of the field wiring.
•
The 3 wire connection method produces a constant offset. The temperature
reading for a Platinum 100
Ω
RTD will read under by about 1°C for the 3m
cable and 3°C for the 8m cable."
•
For optimum accuracy 4 wire connections are recommended..
Figure 7–2 R & RTD Connection to Field Terminals
RTD
M0+
M0-
I0+
M0+
I0-
2 WIRE RTD
I0-
3 WIRE RTD
M0-
I0+
TB1
1
2
3
4
5
RTD
RTD
SH0
I0-
SH0
TB1
1
2
3
4
5
I0+
SH0
TB1
1
2
3
4
5
M0-
M0+
4 WIRE RTD
Содержание ET 200M
Страница 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Страница 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Страница 26: ......
Страница 78: ...8 Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 78 A5E00482820 12 ...
Страница 136: ......
Страница 154: ...6 Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 154 A5E00482820 12 ...
Страница 166: ......
Страница 196: ......
Страница 236: ......
Страница 252: ......
Страница 270: ...8 Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 270 A5E00482820 12 ...
Страница 278: ......
Страница 284: ...Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I O Modules 284 A5E00482820 12 ...