Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-09
27
2
Installation
This section describes installation of the ET200M Marshalled Termination
Assemblies. Topics include: installation considerations and mechanical and
electrical installation.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, and D OR non-
hazardous locations only. Combinations of equipment in your system are subject to
investigation by the local Authority having jurisdiction at the time of installation.
Installations shall comply with the latest edition of the manufacturer’s instruction manual.
Note
•
The installation shall comply with the relevant requirements of the National
Electrical
Code
®
(ANSI/NFPA 70) and all other applicable construction and
electrical codes.
•
For Class I, Div 2 locations, power, input and output (I/O) wiring must be in
accordance with Class I, Div. 2 wiring methods per Article 501-10B of the
National Electrical Code.
•
Refer to Use of subassemblies/modules in a Zone 2 Hazardous Area Product
Information document (19692172) for information on installations in hazardous
locations.
•
Tampering and replacement with non-factory components may adversely
affect the safe use of the system.
Refer to the Preface for Agency Approvals as necessary. Use of the equipment in a
manner not specified by the manufacturer may impair the protection provided by
the equipment.
!
Warning
Electrical shock hazard
•
An electrical shock hazard exists for Relay Output MTAs only when connected
to loads with voltage > 30V rms and 42.4V peak or 60V dc
•
Remove power from all wires and terminals before working on equipment.
Содержание ET 200M
Страница 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Страница 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Страница 26: ......
Страница 78: ...8 Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 78 A5E00482820 12 ...
Страница 136: ......
Страница 154: ...6 Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 154 A5E00482820 12 ...
Страница 166: ......
Страница 196: ......
Страница 236: ......
Страница 252: ......
Страница 270: ...8 Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 270 A5E00482820 12 ...
Страница 278: ......
Страница 284: ...Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I O Modules 284 A5E00482820 12 ...