Technical Specifications
Technical Specifications for 8-Channel HART Analog Input MTA
(6ES7650-1AA61-2XX0)
Dimensions - See Section 1, Figure 1.3, Short Version
Mounting
DIN Rail
35mm ( deep or shallow; with panel mounted
DIN rail only deep)
Power Input
Voltage Input for Single or Redundant Feed
21.6 to 28.8 VDC
Current Consumption (nominal ratings; all inputs
2-wire transducers at 20mA, redundant modules)
0.29 A maximum
Power Dissipation (typical)
1 W
Terminal Block Wire Sizes
Wire Size – US
24 – 14 AWG
Wire Size – Metric
0,205 – 2,08 mm sq.
Electrical Isolation
Between the channels and shield
Yes
Between the channels
No
Between the channels and load voltage L+
For 2-wire transducer: No
4-wire transducer: Yes
Between the shield and load voltage L+
Yes
Permissible potential difference
Between the channels and shield (U
ISO
)
75 VDC
60 VAC
Between the channels and load voltage L+
For 4-wire transducer: 75 VDC
60 VAC
Between the channels
Permissible common-mode voltage with a 4-
wire transducer: 60 VAC
Between the shield and load voltage L+
75 VDC
60 VAC
Insulation tested
Channels to shield and load voltage L+
With 500 VDC, MTA jumper must be in 4 wire
position
Shield to load voltage L+
With 500 VDC
Between the channels
No
Fuse Ratings / Current Limiting
Module
0.5 A (Bussmann P/N: GMA-0.5A)
(Siemens Spare P/N: A5E01568885)
Channel (2 wire transducer connection)
short circuit current about 40 - 60 mA
Characteristic Data of Transducer Supply
Output voltage for transducer and field wiring at
22 mA
(125
Ω sense resistor on modules already taken
into account)
≥
15 V (at Un = 24 V)
Содержание ET 200M
Страница 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Страница 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Страница 26: ......
Страница 78: ...8 Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 78 A5E00482820 12 ...
Страница 136: ......
Страница 154: ...6 Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 154 A5E00482820 12 ...
Страница 166: ......
Страница 196: ......
Страница 236: ......
Страница 252: ......
Страница 270: ...8 Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 270 A5E00482820 12 ...
Страница 278: ......
Страница 284: ...Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I O Modules 284 A5E00482820 12 ...