16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
245
18.9
Technical Specifications for 16-Channel, 24 VDC
Discrete Output Module (6ES7 322-8BH01-0AB0)
18.10 Typical Load Connection to Field Terminals
Figure 18–2 16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA Load Connection to
Field Terminals
NO0
NC0
COM0
NO1
NC1
COM1
120 – 230 Vac
Supply
120 – 230 Vac
Load
fuse
Load powered when output energized
Load powered when output de-energized
120 – 230 Vac
Supply
120 – 230 Vac
Load
fuse
Note
•
Fuse is external to the MTA and not included.
•
Fuse should be sized appropriately for the load.
Note
For a complete functional description and the most current technical specifications
for this module, refer to the manual SIMATIC ET 200M Signal Modules for
Process Automation (document number A5E00085262-04).
Содержание ET 200M
Страница 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Страница 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Страница 26: ......
Страница 78: ...8 Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 78 A5E00482820 12 ...
Страница 136: ......
Страница 154: ...6 Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 154 A5E00482820 12 ...
Страница 166: ......
Страница 196: ......
Страница 236: ......
Страница 252: ......
Страница 270: ...8 Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 270 A5E00482820 12 ...
Страница 278: ......
Страница 284: ...Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I O Modules 284 A5E00482820 12 ...