Installation
Marshalled Termination Assemblies for ET200M Remote I/O Modules
32
A5E00482820-12
2.3
Installation Procedure
2.3.1
Without Cover and Frame
Step
Action
1
Mount the MTA to the DIN rail (Recommend 35mm x 15mm Top Hat style)
2
For EMC Compliance connect the MTA Shield stud to earth ground.
3
Plug the interconnecting cable into the PCS7 I/O Modules
4
For analog I/O Modules: Install shield connecting element, strip a section of outer
insulation from interconnecting cable and place in shield connecting element
5
Plug the interconnecting cable into the D25 or D50 on the MTA
6
Plug the Field terminal connectors into the MTA
7
Plug the IO power connector into the MTA
8
Apply power
2.3.2
With Cover and Frame
Refer to Figures 1-2 and 2-1
Step
Action
1
Mount the MTA to the DIN rail (Recommend 35mm x 15mm Top Hat style)
2
Remove cover using screw driver to disengage the cover retaining tabs from cover.
3
For EMC Compliance remove the Shield Stud Break-Away Tabs (Fig 1-2) on the
frame adjacent to the shield stud to connect the MTA Shield stud to earth ground.
4
Plug the interconnecting cable into the PCS7 I/O Modules.
5
For analog I/O Modules: Install shield connecting element, strip a section of outer
insulation from interconnecting cable and place in shield connecting element.
6
Plug the interconnecting cable into the D25 or D50 on the MTA. Remove the
Module 2 Break-Away Connector Cover (Fig 2-1) to access the connector for module
2 for redundant configurations.
7
Plug the Field terminal connectors into the MTA.
8
Remove the Power Connection Break Away Tabs (Fig 2-1) on the frame adjacent to
the power connection and plug the IO power connector into the MTA.
9
If the Power Monitor Board is used, remove the Power Monitor Break-Away Tabs
(Fig 2-1) on the frame adjacent to the Power Monitor Board connector and connect
to the Power Monitor Board.
10 Snap cover into place
11 Apply power
Содержание ET 200M
Страница 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Страница 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Страница 26: ......
Страница 78: ...8 Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 78 A5E00482820 12 ...
Страница 136: ......
Страница 154: ...6 Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 154 A5E00482820 12 ...
Страница 166: ......
Страница 196: ......
Страница 236: ......
Страница 252: ......
Страница 270: ...8 Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 270 A5E00482820 12 ...
Страница 278: ......
Страница 284: ...Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I O Modules 284 A5E00482820 12 ...