Technical Specifications for 6-Channel F Analog Input HART MTA 6ES7650-1AH62-5XX0
in use with FAIH-module 6ES7336-4GE00-0AB0 and cables 6ES7392-3Bx00-0AU0
Low Demand (PFD) according to SIL 3
(per channel)
High Demand (PFH) according to SIL 3
(per channel)
< 1,45 E-4
< 1,9 E-9 1/h
Proof-test interval
20 years
Note
Fuses are available as spare parts from Siemens.
Fuse information can be found at:
http://www.littelfuse.com
http://www.bussmann.com
11.8
Changes to the Technical Specifications for 6-Channel
F ANALOG INPUT HART Module
(6ES7 336-4GE00-0AB0)
This section contains changes to the I/O module specifications when it is used with the MTA.
Changes for 6-Channel F Analog Input HART MTA
(6ES7650-1AH61-5XX0)
Transmitter Connections
Only 1 transmitter can be connected to a
channel.
Output voltage for 2 wire transducer and cable
with 22 mA transducer current @ 24 V Supply*
non redundant mode: 17 V
redundant mode: 14 V
Fail-safe Performance Characteristics
Adds a dangerous undetected failure rate
6.3 FIT for 6 channels) to the FAI module
in any configuration.
Sensor Supply
The FAI module internal sensor supply
outputs are not used when using the FAIH
MTA.
Protection against short circuit with MTA sensor
supply
No external fuse required. The FAIH MTA
limits current.
* If the output voltage is not sufficient for a 2 wire transmitter, safety barrier and field wiring, it is
recommended that a 4 wire transmitter be used.
Содержание ET 200M
Страница 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Страница 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Страница 26: ......
Страница 78: ...8 Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 78 A5E00482820 12 ...
Страница 136: ......
Страница 154: ...6 Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 154 A5E00482820 12 ...
Страница 166: ......
Страница 196: ......
Страница 236: ......
Страница 252: ......
Страница 270: ...8 Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 270 A5E00482820 12 ...
Страница 278: ......
Страница 284: ...Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I O Modules 284 A5E00482820 12 ...