8-Channel Analog Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
55
Technical Specifications for 8-Channel Analog Input MTA 6ES7650-1AA52-2XX0 in use with
I/O modules 6ES7331-7NF00-0AB0 and cables 6ES7 392-3Bx00-0BA0
Module Accuracy
•
Basic error limit (25
o
C)
voltage mode
current mode
± 0,05%
± 0,15%
•
Operational error limit (overall
temperature range; U_cm = 0V)
voltage mode
current mode
± 0,1%
± 0,4%
•
Operational error limit (overall
temperature range; U_cm = 50V)
voltage mode
current mode
± 0,7%
± 1,0%
Approvals
MTA Agency Approvals
See Preface section, Approvals Table
(in
User's Manual)
Technical Specifications for 8-Channel Analog Input MTA 6ES7650-1AA52-2XX0 in use with
I/O modules 6ES7331-7NF10-0AB0 and cables 6ES7 392-3Bx00-0BB0
Dimensions - See Section 1, Figure 1.3, Short Version
Mounting
DIN Rail
35mm ( deep or shallow; with panel mounted
DIN rail only deep)
Power Input
Voltage Input for Single or Redundant Feed
21.6 to 28.8 VDC
Current Consumption (nominal ratings; all
channels 20mA)
< 0,5 A
Power Dissipation (typical)
1 W
Permissible potential difference
Between the channels
AC 60V / DC 75V
Fuse Ratings / Current Limiting
Module
0.5 A (Bussmann P/N: GMA-0.5-R)
(Siemens Spare P/N: A5E00755625)
Power output for 2-wire transducer supply
Supply current for each channel
typ. 20 mA
Short circuit current
25 … 42 mA
Load capability
> 750
Ω
Open loop voltage
L+
Short circuit protection
electronically; individual for each channel
Power Monitoring System – Optorelay Output Contact Ratings
Threshold voltage
ca. 15 V
Maximum switched Voltage
30 V DC
Maximum switched Current
0.5 A resistive load; not short circuit proofed
Indicators
Input Power
Green LED on when input power available, red
LED on if power supply is reversed
Содержание ET 200M
Страница 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Страница 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Страница 26: ......
Страница 78: ...8 Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 78 A5E00482820 12 ...
Страница 136: ......
Страница 154: ...6 Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 154 A5E00482820 12 ...
Страница 166: ......
Страница 196: ......
Страница 236: ......
Страница 252: ......
Страница 270: ...8 Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 270 A5E00482820 12 ...
Страница 278: ......
Страница 284: ...Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I O Modules 284 A5E00482820 12 ...