8-Channel Analog Input MTA
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12
51
5.5
Installation Requirements
See Section 2,
, before performing any installation and observe all
warnings
Two interconnecting cable types (for Module 6ES7331-7NF00-0AB0: 6ES7922-
3BD00-0BA0 (3m), 6ES7922-3BJ00-0BA0 (8m); for Module 6ES7331-7NF10-
0AB0: 6ES7922-3BD00-0BB0 (3m), 6ES7922-3BJ00-0BB0 (8m))
, supporting eight
analog input channels, connects the analog input termination assembly to the 8-
channel analog input module (6ES7 331-7NF00-0AB0, E-Stand 5 or higher) or to
the 8-channel analog input module (6ES7331-7NF10-0AB0). See Figure 5–1.
It may be necessary to modify the printed circuit board as follows:
•
For channels measuring voltage, move the
I – V
jumper for that channel to the
V
side and the
2 – 4
jumper for that channel to
4
side.
•
For channels measuring current, move the
I – V
jumper for that channel to the
I
side and the
2 – 4
jumper to
2
for using 2 wire transducer or
4
for using 4 wire
transducer.
•
For channels which are connected to a non isolated 4-wire transducer, set the
I
– V
jumper to
I
and the
2 – 4
jumper to 2. (see Figure 5–3)
Note
To disconnect the interconnecting cable shield from ground at the MTA only, cut
and remove the shield disconnect jumpers,
Module1
and
Module2
, for the
associated cable.
5.6
Maintenance
Under normal operation, the
A/B
Power LED
and the fuse status LEDs, are on. If
all are off, check the power supply to the MTA. If the module fuses status LEDs are
off, check the fuses
Module1
and
Module2
of the MTA and replace them if
necessary.
See Section 3,
, before performing any maintenance and observe all
warnings.
Содержание ET 200M
Страница 8: ...Preface Marshalled Termination Assemblies for ET200M Remote I O Modules 8 A5E00482820 12 ...
Страница 16: ...Contents Marshalled Termination Assemblies for ET200M Remote I O Modules 16 A5E00482820 12 ...
Страница 26: ......
Страница 78: ...8 Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 78 A5E00482820 12 ...
Страница 136: ......
Страница 154: ...6 Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 154 A5E00482820 12 ...
Страница 166: ......
Страница 196: ......
Страница 236: ......
Страница 252: ......
Страница 270: ...8 Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I O Modules 270 A5E00482820 12 ...
Страница 278: ......
Страница 284: ...Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I O Modules 284 A5E00482820 12 ...