Commissioning
5.5 Commissioning using the BOP
Control Units CU240S
72
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
Frequency setpoint via fixed frequency (P1000 = 3)
Parameter
Description
Setting
P1016 = 1
Fixed frequency mode, defines
the selection method for fixed
frequencies.
1: direct selection (default)
2: binary coded
P1001 = 0
Fixed frequency 1, (FF1)
Value given in Hz.
P1002 = 5
Fixed frequency 2
P1003 = 10
Fixed frequency 3
P1004 = 15
Fixed frequency 4
P1005 = 20
Fixed frequency 5
P1006 = 25
Fixed frequency 6
P1007 = 30
Fixed frequency 7
P1008 = 35
Fixed frequency 8
P1009 = 40
Fixed frequency 9
P1010 = 45
Fixed frequency 10
P1011 = 50
Fixed frequency 11
P1012 = 55
Fixed frequency 12
P1013 = 60
Fixed frequency 13
P1014 = 65
Fixed frequency 14
P1015 = 65
Fixed frequency 15
P1020 = 722.3 Fixed frequency selection - Bit 0
Selects DI3 for FF selection
P1021 = 722.4 Fixed frequency selection - Bit 1
Selects DI4 for FF selection
P1022 = 722.5 Fixed frequency selection - Bit 2
Selects DI5 for FF selection
P1023 = 722.6 Fixed frequency selection - Bit 3
Selects DI6 for FF selection
The fixed frequency can be selected via four digital
inputs (default DI3 … DI6).
Fixed frequences via direct selection (P1016 = 1):
With the default settings additional combinations as
follows are possible:
3G]
3G]
3G]
3G]
33
33
33
33
33
333
333
333
3333
',3
',3
',3
',3
',',
',',
',',
',',
',',
',',',
',',',
',',',
',',',',
)L[HG)UHTXHQF\
VHOHFWHGYLD
))3DU
))
>+]@
Fixed frequences via binary coded selection
(P1016 = 2):
With binary coded selection each frequency, set in one
of the parameters P1002 … P1015 can be directly
selected.
P1001
P1002
P1003
P1004
P1005
P1006
P1007
P1008
P1009
P1010
P1011
P1012
P1013
P1014
P1015
DI3 (P1020 =722.3)
DI4 (P1021 =722.4)
DI5 (P1022 =722.5)
DI6 (P1023 =722.6)
DI3, DI4
DI4, DI5
DI5, DI6
DI3, DI5
DI4, DI6
DI3, DI6
DI3, DI4, DI5
DI4, DI5, DI6
DI3, DI5, DI6
DI3, DI4, DI6
DI3, DI4, DI5, DI6
0
5
10
15
20
25
30
35
40
45
50
55
60
65
65
Fixed Frequency
selected via
FF-
Par
FF-default
setting
[Hz]