Commissioning
5.5 Commissioning using the BOP
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
69
Assigning digital inputs
Parameter
Description
Setting
P0701 = 1
Terminal 5:
Digital Input 0 (DI0)
P0702 = 12
Terminal 6:
Digital Input 1 (DI1)
P0703 = 9
Terminal 7:
Digital Input 2 (DI2)
P0704 = 15
Terminal 8:
Digital Input 3 (DI3)
P0705 = 16
Terminal 16:
Digital Input 4 (DI4)
P0706 = 17
Terminal 17:
Digital Input 5 (DI5)
factory settings for
CU240S
P0707 = 18
Terminal 40:
Digital Input 6 (DI6)
P0708 = 0
Terminal 41:
Digital Input 7 (DI7)
P0709 = 0
Terminal 42:
Digital Input 8 (DI8)
factory settings for
CU240S
not availble with
CU240S DP-F
Possible values for P0701 to P0709:
0: Digital input disabled
1: ON/OFF1
2: ON reverse /OFF1
3: OFF2 - coast to standstill
4: OFF3 - quick ramp-down
9: Fault acknowledge
10: JOG right
11: JOG left
12: Reverse
13: MOP up (increase frequency)
14: MOP down (decrease frequency)
15: Fixed frequency selector bit0
16: Fixed frequency selector bit1
17: Fixed frequency selector bit2
18: Fixed frequency selector bit3
25: DC brake enable
27: Enable PID
29: External trip
33: Disable additional freq setpoint
99: Enable BICO parameterization
P0724 = 3
Debounce time for digital inputs
Defines the debounce time (filtering time) used for digital inputs.
0: No debounce time
1: 2.5 ms debounce time
2: 8.2 ms debounce time
3: 12.3 ms debounce time (default)
P9603 = 00
Terminal 62, 63: SLS via FD1A and FD1B
P9603 = 01
Terminal 60, 61: SLS via FD0A and FD0B
P9603 = 02
Terminal 62, 63: SS1 via FD1A and FD1B
P9603 = 03
Terminal 60, 61: SS1 via FD0A and FD0B
P9603 = 04
Terminal 62, 63: STO via FD1A and FD1B
P9603 = 05
Terminal 60, 61: STO via FD0A and FD0B
not availble with CU240S and CU240S DP