Communication
6.5 Communication via PROFINET
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
171
Adding a SINAMICS G120 inverter to HW Config
To add the SINAMICS G120 inverter as a PROFINET IO device, perform the following steps:
1.
Select the PROFINET sub-network in HW config.
2.
Open "PROFINET IO > Drives > SINAMICS > GSD" in the hardware catalog.
3.
Double click onto e.g. "SINAMICS G120 CU240S PN F" to add the G120 inverter as I/O
device to the subnet.
Setting the properties of the G120 inverter as PROFINET I/O device
Double click SINAMICS G120 in the station window to open the properties dialog then:
● Assign a unique device name or accept the name, the system offers.
● Assign an IP adress or accept the one, the system offers (standard setting).
● Confirm your settings with OK.
Selecting a telegram
Note
The inverters are able to operate with different telegram types. The telegram, selected in the
inverter via P0922, must be identical to the type selected in HW Config.
1.
Open "PROFINET IO > Drives > SINAMICS > GSD > Relevant drive" in the hardware
catalog
2.
Select the telegram and add it, e.g. by double click, to the sub-slot in the station window.