Commissioning
5.5 Commissioning using the BOP
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
67
Note
If P0014=0 it is possible to transfer all parameter values from RAM into EEPROM via P0971.
The duration of the data transfer depends on the number of changed parameters. The data
transfer can last up to 3 minutes. During the data transfer, BOP displays "bUSY".
Pulse Encoder
Parameter
Description
Setting
P0400 = 0
or
P0400 = …
Select encoder type *
0: Disabled (no encoder fitted; default)
2 or 12: Two quadrature encoder (two channels)
P0408 = …
Number of encoder pulses (Only if encoder is fitted)
Enter the number of encoder pulses per revolution. The number of encoder pulses per
revolution P0408 is limited by the maximum pulse frequency of the pulse encoder module
(f
max
= 300 kHz)
Temperature Sensor
Parameter
Description
Setting
P0601 = 0
or
P0601 = …
Motor temperature sensor
0: No sensor (default;→ P0610)
1: PTC thermistor (→ P0604)
2: KTY84 (→ P0604)
4: ThermoClick sensor(→ P0604)
P0604 = …
Threshold motor temperature (0 °C … 220 °C, default 130 °C)
Enter the warning threshold for motor over temperature protection. The trip temperature
threshold (warning thr 10 %) is where either the inverter is tripped or Imax is reduced
(P0610).
P0610 = 2
Motor I2t temperature reaction
Defines the reaction when the motor temperature reaches the warning threshold.
0: No action, only a warning
1: Warning and I
max
reduced (this results in a reduced output frequency)
2: Warning and trip (F0011) (default)