Standard application AHU
CE1P3977en_02
Building Technologies
HMI
01.02.2010
17.15.20
Cooling > Pump
Main Index > Unit > Temp control > Cooling > Cooling pump
Parameter
Function
Value range
Unit
Standard R
S Link
Command
Cooling status
On…Off
X
Fdbk
Cooling Pump Feedback
Nofdbk…fdbk
X
Alarm
Cooling Pump alarm
Ok…alarm
X
Start up delay fdbk
After this Time the Feedback has to be
TRUE
0…36000
6
Section:
5.10.2
Off by fdbk alarm
In case of a Feedback alarm the Pump is
switched Off
No…Yes
Yes
6
Min run time
Mnimum On Time after a Start
0…36000
180
6
Kick date / time
Pump Kick Date and Time
6
Section:
Kick interval
Intervall Time for Pump Kick
0.0…36000.0
h
168.0
6
5.10.3
Kick on time
Pulse for Pump Kick
0…36000
--- S ---
60
6
17.15.21
Cooling > Direct expansion
Main Index > Unit > Temp control > Cooling > DX
Parameter
Function
Value range
Unit
Standard R
S Link
Command
Dx Cooling Command
On…St3
Feedback
Dx Cooling Feedback
Nofdbk…fdbk
Alarm
Dx Cooling alarm
OK…ALarm
Start up delay fdbk
Dx Cooling Feedback Start up Delay
0…36000
--- S ---
30
6
Min run time
Min Run Time of Dx Cooling
0…36000
--- S ---
60
6
Min off time
Min Off Time of Dx Cooling
5…600
--- S ---
120
6
Section:
Min stage time
Min Stage Time of Dx Cooling
5…600
--- S ---
360
6
5.10.4
Start stage 1
Start point Electrical heating Stage 1
0…100
%
20
6
Start stage 2
Start point Electrical heating Stage 2
0…100
%
40
6
Start stage 3
Start point Electrical heating Stage 3
0…100
%
80
6
Stage hys off
Hysteresis to switch Off a Stage
0…20
%
10
6
17.15.22
Cooling > Max limitation fan
Main Index > Unit > Temp control > Cooling > Clg max limit fan
Parameter
Function
Value range
Unit
Standard R
S Link
Fan stage 0
Only visible if plant is not configured, not
used! Fix setted to 0
0…100
%
0
6
Fan stage 1
Max Output Value for Stage 1
0…100
%
100
6
Section:
Fan stage 2
Max Output Value for Stage 2
0…100
%
100
6
0
Fan stage 3
Max Output Value for Stage 3
0…100
%
100
6
17.15.23
Heating 2
Main Index > Unit > Temp control > Heating 2
Parameter
Function
Value range
Unit
Standard R
S Link
Controller
Heating Controller; Jumpline to settings
0…100
%
X
Output Signal
Heating Valve Position; Jumpline to settings 0…100
%
X
Extra Seq setpoint
Extra Setpoint (only activ if Htg 2 or Clg 2 or
ElHtg 2 is selected as Stand alone; this
Setpoint is valid for all)
0…99
°C
20.0
6
Frost protection
Actual Status; Jumpline for Frost Function
settings
Passive…Active
%
6
Section:
Pump.
Actual Value; Jumpline for Pump Function
settings
0…100
6
5.8.1
Pre heating
Actual Status; Jumpline for Pre heating
Function settings
On…Off
6
Frost protection
Actual Status; Jumpline for Frost Function
settings
Passive…Active
6
Frost monitor
Actual Status of Htg frost protect Monitor
OK…Frost
6
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 203