137 / 244
Siemens
Standard application AHU
CE1P3977en_02
Building Technologies
Save / restore parameters
01.02.2010
Reset required !!
−
−
Execute
Resets after downloading parameters.
−
Passive position.
−
Reset. The controller operate using the con-
figuration loaded from the SD card.
Par service load
−
−
Execute
Requires access level 6.
Downloads parameter files from commissioning.
−
Passive position.
−
Download. The display than returns to
ser-
vice load.
Par factory load
−
−
Execute
Requires access level 4.
Downloads parameter files from factory.
−
Passive position.
−
Download. Display returns to
.
Par service save
−
−
Execute
Requires access level 4.
Saves parameter files from the commissioning to
the controller.
−
Passive position.
−
Save. Display returns to
.
Par factory save
−
−
Execute
Requires access level 2.
Saves parameter files from factory.
−
Passive position.
−
Save. Display returns to
.
Application default
−
−
Execute
Requires access level 2.
Download configuration with all parameters per
the overall standard program loaded at the fac-
tory. Requires complete re-commissioning!
−
Passive position.
−
Download. Display returns to
.