200 / 244
Siemens
Standard application AHU
CE1P3977en_02
Building Technologies
HMI
01.02.2010
17.15.7 Min/max ctrlr sply
Main Index > Unit > Temp control > Min/max ctrlr sply
Parameter
Function
Value range
Unit
Standard R
S Link
Min controller
Actual Value Minimum Controller; Jumpline
to settings
0…100
%
X
Max controller
Actual Value Maximum Controller; Jumpline
to settings
0…100
%
X
Section:
5.5.5
Min setpoint
Setpoint for the min Controller
15…26
°C
17.0
6
Max setpoint
Setpoint for the max Controller
17…50
°C
27.0
6
17.15.8 Hrec damper
Main Index > Unit > Temp control > Hrec damper
Parameter
Function
Value range
Unit
Standard R
S Link
Controller
Heat Recovery Damper Controller; Jumpline
to settings
0…100
%
X
Output signal
Heat Recovery Damper Position; Jumpline
to settings
0…100
%
X
Section:
Recovery value
Heat Recovery Value
0…100
%
0.0
6
5.6
Min fresh air
Min Open of Heat Recovery Damper
0…100
%
20
6
Start up time
Start up Time for Heat Recovery Damper
0…600
--- S ---
60
6
Start up tmp
Start Up Temperature for Heat Recovery
Damper
-64…64
°C
15.0
6
17.15.9 Heat recovery
Main Index > Unit > Temp control > Heat recovery
Parameter
Function
Value range
Unit
Standard R
S Link
Controller
Heat Recovery Controller
0…100
%
X
Output signal
Heat Recovery Position
0…100
%
X
Command
Heat Recovery status
On…Off
X
Pump / cmd
Pump Status; Jumpline for settings
On…Off
Aalarm
Heat Recovery alarm
OK…alarm
X
Frost monitor
Heat Recovery Frost monitor
OK…Frost
X
Section:
Frost protection
Jumpline for Frost protection settings
0…100
%
6
5.7.1
Frost protect press
Jumpline for settings
X
Efficiency
Heat Recovery Efficiency
0…100
%
X
Start up time
For this Time the Hrec run with 100% at
Startup
0…600
--- S ---
60
6
Start up tmp
If the Outside temperature is lower or equal
this Value the Hrec do run for Start up time
-64…64
°C
15.0
6
Max speed defrost
Maximum allowed speed in case of Frost
(monitor = Frost)
0…100
%
20
6
17.15.10
Heat recovery > Hrec (pump) cmd
Main Index > Unit > Temp control > Heat recovery > Pump / cmd
Parameter
Function
Value range
Unit
Standard R
S Link
Command
Heat Recovery status
On…Off
X
Fdbk
Heat Recovery Pump Feedback
Nofdbk…fdbk
X
Alarm
Heat Recovery Pump alarm
Ok…alarm
X
Section:
Start up delay fdbk
After this Time the Feedback has to be
TRUE
0…36000
6
5.7.2
Off by fdbk alarm
In case of a Feedback alarm the Pump is
switched Off
No…Yes
Yes
6
Min run time
Mnimum On Time after a Start
0…36000
180
6
Kick date / time
Pump Kick Date and Time
6
Section:
Kick interval
Intervall Time for Pump Kick
0.0…36000.0
h
168.0
6
5.7.3
Kick on time
Pulse length for Pump Kick
0…36000
--- S ---
60
6
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 200