BC8001A Installation and Operating Instruction
Page 49/49
3. Fuse Replacement
Name
Model
Replacement
Battery fuse capacity
10A
Replace the same model product
AC fuse capacity
5A
Replace the same model product
For problems with other components, please contact manufacturer for replacement.
4. Battery Maintenance
Perform the following tests at the recommended interval. Replace the battery set every four years or if any of the test criteria are
not met.
Initiation/Reacceptance:
1. Charge Test - With the batteries fully charged and connected to the charger, measure the voltage across the battery set. It
must read 26.0VDC
±
0.3V.
2. Discharge Test – With full system alarm load, the voltage on a fully charged battery must not fall below 20.4VDC after 30
minutes.
3. Load Voltage Test – With full system alarm load, the voltage on a fully charged battery must not fall below 24.0VDC after 1
minute.
Testing Interval:
1. Semiannually – Perform the Load Voltage Test
2. Annually – Perform the Charger Test and Discharge Test
5. Reclamation