BC8001A Installation and Operating Instruction
Page 12/49
5. Battery
Wiring as refer to figure 6.
Maximum battery circuit
current
Charging: 3.1A
Discharging:6A
Capacity
Sealed Leaded
Acid,12VDC,12Ah×2
Expected battery standby
operational times
24 Hours and 5 Minutes alarm
Dimension(mm)
181×76×167(L×W×H)
Battery Maintenance
Check battery regularly, if the following things happen, eg.
function is not normal, housing is distorted, liquid releases,
the battery must be changed. If the battery is dirty, please
use towel with warm water to clean it. Do not use petrol, or
chemical liquid.
To be stored at -10
℃
~ +50
℃
temperature and dry place.
To be stored at full chargeable status. To be charged before being used because of self discharge.
6. Power supply load calculation table
No
.
Type
Description
Quantity Quiescent
current(mA)
Max.
current(mA)
Total Quiescent
current(mA)
1. BDS031A
Addressable heat detector
0.8
1.0
2. BDS051A
Addressable smoke detector
0.8
1.0
3. BDS121A
Manual signaling box
0.8
1.0
4. BCC8001A
Main Board+CPU
90.0
130.0
5. BDS132A
Input Module
1.0
3.0
6. BDS221A
Output Module
1.0
3.0
7.
NAC
0
1500.0
8. U-MCS
Multicandela selectable strobe(red)
0
145.0
9. U-MMT-MCS Multitone horn Strobe(red)
0
200.0
10. DSC
Dual sync control module
0
55.0
11. P2475
SpectrAlert horn/strobe
0
245.0
12. MDL
Sync-Circuit module
0
12.0
Total System Current
-
+
-
+
Power Supply
Bat- Bat+
Battery
Battery
Figure 6
Battery and AC power connection diagram