BC8001A Installation and Operating Instruction
Page 22/49
8. Isolation Event Handling
Status:
LCD will display isolation event automatically as “Isolation Screen”.
The isolation LED is on.
Acknowledge LED is flashing.
The buzzer is sounding.
How to do:
1. Press “Acknowledge” button to acknowledge the isolation:
If current user level is 1, login window will be popup automatically. After inputting
level 2/3 password, press “OK” to enter trouble window. All isolation events are
acknowledged at the same time.
-
Symbol “*“ will be changed to “#” automatically
-
Buzzer is silent
-
Acknowledge LED will change from flashing to steady
If current user level is 2/3, all isolation events are acknowledged at the same
time.
-
Symbol “*“ will be changed to “#” automatically
-
Buzzer is silent
-
Acknowledge LED will change from flashing to steady
When the isolated point is open, the panel will revert to normal status.
Isolation Screen
9. Activation Event Handling
Status:
LCD will display activation event automatically as “Activation Screen”.
The activation LED is on.
Acknowledge LED is flashing.
The buzzer is sounding.
How to do:
1. Press “Acknowledge” button to acknowledge the activation:
If current user level is 1, login window will be popup automatically. After inputting
level 2/3 password, press “OK” to enter trouble window. All activation events are
acknowledged at the same time.
-
Symbol “*“ will be changed to “#” automatically
-
Buzzer is silent
-
Acknowledge LED will change from flashing to steady
If current user level is 2/3, all activation events are acknowledged at the same
time.
-
Symbol “*“ will be changed to “#” automatically
-
Buzzer is silent
-
Acknowledge LED will change from flashing to steady
When the activated point is de-activated, the panel will revert to normal status.
Activation Screen
<RT – Isolation:1> L1 A
- 1 Room 102 heat detector
<RT – Active:1> L1 A
- 1 Floor 02 BDS221(A) Outpu