BC8001A Installation and Operating Instruction
Page 4/49
2. Performance Parameters
Items
Standard
Configurations
Extension
Configurations
Number of detector lines (polarity free)
1
2
Number of field devices
127
254
LCD display
240
×
128 pixel, back light
Digital I/O’s
Nr. of monitored OC output
(400 to 2K ohms @24VDC)
1
Nr. of monitored inputs
2
Nr. of monitored NAC (1.5A @24VDC)
1
Number of history records
1000
Automapping
Yes
AC power input
120/240VAC, 60/50Hz
Regulated DC output
24VDC
Battery-backup
Sealed Lead Acid,12VDC,12Ah
×
2
Upload/download port
USB 1.1
Dimensions, in mm
369
×
266
×
200
(
W
×
H
×
D
)
Weight (excluding battery), in: kg
6.5
Alarm response time
<10s
AC fuse capacity
5.0A
Battery fuse capacity
10.0A
Operating temperature
0
℃
~
+49
℃
Storage temperature
–10
℃
~
+50
℃
Relative humidity
≤
93%(32
±
2
℃
)
Usage place
Indoor and dry
3. BC8001A External Structure