BC8001A Installation and Operating Instruction
Page 35/49
Editable Parameters of Different Point
Point Type
Parameter
Default Value
Optional Value
BDS051(A) Smoke Detector
Sensitivity
Standard
1: Low
2: Standard
3: High
BDS221(A) Output Module
Supervision Time:
30s
30…600 Seconds
Supervision time: Define the waiting-for-
confirmation time of activated output
equipment (if the controller still cannot
receive a confirmation signal by timeout,
it will display ”active with no confirma-
tion”. Otherwise it will display” active
with confirmation”.)
Work Mode
Steady
BDS132(A) Alarm Input
BDS132(A) Tech Input
Alarm Input
Technical Input
Dry Contact Alarm Input
Dry Contact Technical Input
Filter
3
1…7
NAC
Work Mode
Steady
Steady
Pulse(60 per min)
Pulse(120 per min)
Bongs