Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
110
Equipment Manual, 07.2021, A5E37775406-11-76
0x0005: Battery information parameters (reading)
Data
Description
Data type
Number of batteries
Number of connected battery modules. Here, only SITOP BAT1600
or SITOP UPS1100 battery modules (SITOP system batteries) are
counted.
Unsigned8
Fill byte(s)
-
3 x Unsigned8
Batt 1: Standby time [1 s]
Standby time
Unsigned32
Batt 1: Buffer time [1 s]
Time in buffer mode
Unsigned32
Batt 1: Total charging current
[1 mAh]
Total charge level (battery-specific data): Total charge within the
service life of the SITOP UPS1600.
Unsigned32
Batt 1: Total culled current [1 mAh] Total charge level used (battery-specific data): Total discharge over
the service life of the SITOP UPS1600.
Unsigned32
Batt 1: EOCV [0.01 V]
"End-of-charge voltage": Battery voltage when charging changes to
trickle charging. The energy storage device is then charged up to
100 %.
Unsigned16
Batt 1: Charge current [1 mA]
Charge current: Current magnitude used to charge the connected
battery modules during the constant current charging phase.
Unsigned16
Batt 1: Battery capacity [0.1 Ah]
Battery capacity: Total battery capacity of all energy storage devic-
es connected to the SITOP UPS1600.
Unsigned16
Batt 1: Stop buffering voltage
[0.01 V]
Battery voltage, which when fallen below, buffer mode is exited
(stop buffering voltage).
Unsigned16
Batt 1: Battery type
Battery type
Unsigned8
Batt 1: Minimal temperature [1 °C] Lowest specified operating temperature of the SITOP BAT1600 or
SITOP UPS1100 battery module being used
Signed8
Batt 1: Maximal temperature [1 °C] Highest specified operating temperature of the SITOP BAT1600 or
SITOP UPS1100 battery module being used
Signed8
Fill byte(s)
-
1 x Unsigned8
Batt 1: Order number
Order number (Article number).
VisibleString(20)
Batt 1: Serial number
Serial number
VisibleString(16)
Batt 1: Manufacturing date
Manufacturing date
VisibleString(8)
Batt 1: Version number
Version number
VisibleString(6)
Batt 1: Calculated battery health
Calculated battery health
Unsigned8
Batt 1: Operating state
Operating state
Unsigned8
Batt 1: LED state
LED states
Unsigned8
Fill byte(s)
-
3 x Unsigned8
Batt 1: SWD
SW revision
Unsigned32
Batt 1: Battery MID
Battery Module Ident Number
Unsigned32
Batt 2: Standby time [1 s]
Standby time
Unsigned32
Batt 2 Buffer time [1 s]
Time in buffer mode
Unsigned32
Batt 2: Total charging current
[1 mAh]
Total charge level (battery-specific data): Total charge within the
service life of the SITOP UPS1600.
Unsigned32
Batt 2: Total culled current [1 mAh] Total charge level used (battery-specific data): Total discharge over
the service life of the SITOP UPS1600.
Unsigned32
Batt 2: EOCV [0.01 V]
"End-of-charge voltage": Battery voltage when charging changes to
trickle charging. The energy storage device is then charged up to
100 %.
Unsigned16
Batt 2: Charge current [1 mA]
Charge current: Current magnitude used to charge the connected
battery modules during the constant current charging phase.
Unsigned16
Batt 2: Battery capacity [0.1 Ah]
Battery capacity: Total battery capacity of all energy storage devic-
es connected to the SITOP UPS1600.
Unsigned16
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...