Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
124
Equipment Manual, 07.2021, A5E37775406-11-76
0x0041: Web server parameters (reading/writing)
Data
Description
Data type
WebserverEnabled
Activating/deactivating the web server of the SITOP UPS1600:
•
0: disable
•
255: enable
Unsigned8
AutoReloadEnabled from V2.1
Enable/disable automatic update:
•
0: disable
•
255: enable
Unsigned8
ReloadTime from V2.1
Update interval:
•
0: Off
•
5: 5s
•
10: 10s
•
20: 20s
•
30: 30s
•
60: 60s
Unsigned8
AutoLogout from V2.1
Enable/disable automatic logoff:
•
0: disable
•
255: enable
When automatic logoff is activated, the logged on user ("Guest" or
"Admin") is automatically logged off when the SITOP UPS1600 web
server is inactive for 15 minutes.
Unsigned8
HttpAccessEnable from V2.1
Enable/disable HTTP access:
•
0: disable
•
255: enable
Unsigned8
Fill byte(s) from V2.1
-
Unsigned8
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...