Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
43
Signaling
6EP4134-3AB00-…
6EP4136-3AB00-…
6EP4137-3AB00-…
Off
Module runs up, DC-UPS defective (critical hardware fault)
Green
Battery module OK
Flashing yellow
(1/1)
Battery outside the permitted temperature range
Yellow
Selected buffer time cannot be attained
Red
Battery module fault, maintenance required (incorrect polarity, battery
module not connected, high ohmic battery module connection, battery
deep discharged, fuse defective/ruptured, asymmetrical cell voltage, battery
R test unsuccessful)
LED 5 and LED 6 (PROFINET LEDs)
Signaling
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
6EP4137-3AB00-2AY0
LED 5 (SF)
LED 6 (RUN)
Off
Off
No connection to a PROFINET IO controller
Off
Flashing green
(0.5/0.5)
Configuration by the PROFINET IO controller
Off
Green
Application started successfully, module O.K.
Red
Green
Application started successfully, module not O.K.
Flashing red
(0.1/0.1)
Green
Application in progress, diagnosis can be called
Flashing red
(0.5/0.5)
Flashing green
(0.5/0.5)
Self-test running (flashing alternately every 3 s)
Flashing red
(0.5/0.5)
Off
DCP device identification (LED flashes for
3 seconds)
Flashing red
(0.5/0.5)
Flashing green
(0.5/0.5)
Firmware update
LEDs 5 and 6 are active only for ... -2AY0.
LED 7 (Ethernet LED /P2)
Signaling
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
6EP4137-3AB00-2AY0
Off
Device not connected with controller
Green
Device connected with controller, no activity
Green/yellow, alternat-
ing
Device connected with controller, send/receive data (RX/TX)
Yellow
Device connected with controller, active communication (RX/TX)
LED 7 is active only for ... -2AY0
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...