Engineering and remote access
3.10 OPC UA server
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
171
Display name
Data type
Definition
Description
BufferingEndVoltage
Setpoint
Float
AnalogItemType When battery voltage is lower than this voltage, the battery
charge is no longer sufficient. Buffering is stopped.
BufferingValid
SupplyVoltage
TimeSetpoint
Float
AnalogItemType When the SITOP UPS1600 is in buffer mode, time for which
the input voltage must be OK again before SITOP UPS1600
buffering is stopped and connected devices are operated
again with input supply.
DischargeCutOff
VoltageSetpoint
Float
AnalogItemType Voltage, where discharge of the battery is cut off
3.10.6.10
Charging
Display name
Data type
Definition
Description
ChargingCurrent
Setpoint
Float
AnalogItemType Charge current
ChargeEndVoltage
Setpoint
Float
AnalogItemType Battery voltage when charging changes to trickle charging.
The battery is charged 100 %.
DisableChargingSet-
point
Boolean
PropertyType
Battery charging deactivated
MaximumAllowed
ChargeCurrentSetpoint
Float
AnalogItemType Setting the max. charge current
3.10.6.11
General
Display name
Data type
Definition
Description
AlarmInvalidSupply
VoltageTimeSetpoint
Float
AnalogItemType Alarm filter: an alarm is only sent if it is pending for longer
than the configured time
DeviceOutputEnable
Setpoint
Boolean
PropertyType
DeviceOutputEnableSetpoint
ResetEnableSetpoint
Boolean
PropertyType
When input voltage returns during buffering, the output is
switched off for a configurable time in order to reset con-
nected devices.
ResetTimeSetpoint
Byte
AnalogItemType Time for which the output of SITOP UPS1600 is switched off
when connected devices are reset.
ResistorTestInterval
Setpoint
Byte
AnalogItemType Battery test interval
3.10.6.12
Hardware
Display name
Data type
Definition
Description
HardwareBattery
ProfileClamp
Enumeration
MultiState
DiscreteType
The charge characteristic for batteries on signal terminals is
set. This setting is only applied if hardware settings are ef-
fective.
HardwareBuffer
ThresholdSwitch
Enumeration
MultiState
DiscreteType
Trigger voltage for buffering - buffering is activated below
this value
HardwareBuffer
TimeSwitch
Enumeration
MultiState
DiscreteType
Desired buffering time before device switches off
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...