Engineering and remote access
3.10 OPC UA server
SITOP UPS1600 / BAT1600 / UPS1100
176
Equipment Manual, 07.2021, A5E37775406-11-76
ActualState
Display name
Data type
Definition
Description
BatteryCalculated
Health
Byte
AnalogItemType Calculated battery state (only for SITOP BAT1600)
BatteryOperatingState Byte
AnalogItemType Battery status (only for SITOP BAT1600)
ModuleCapacity
Float
AnalogItemType Battery capacity: Total battery capacity of all energy storage
devices connected to the SITOP UPS1600.
ModuleChange
Recommended
Boolean
PropertyType
Battery capacity is insufficient to achieve the specified buffer
time.
ModuleCompound
Enumeration
MultiState
DiscreteType
Connected device
ModuleConnection
Fault
Boolean
PropertyType
Connection to battery interrupted - check connection and
fuse
ModuleManufactoring
Date
Date
PropertyType
Manufacturing date
ModuleMax
Temperature
Sbyte
AnalogItemType Maximum specified operating temperature of the battery.
ModuleMin
Temperature
Sbyte
AnalogItemType Minimum specified operating temperature of the battery.
ModuleStandbyTime
UInt32
AnalogItemType Battery-specific data: Time for which battery was connected
but no power was consumed.
ModuleStateLed
Object
Sitop_1600_
LedType
ModuleStateLed
ModuleTemperature
Sbyte
AnalogItemType Battery temperature
Alarm
Display name
Data type
Definition
Description
AlarmBatteryChange
Canceled
Boolean
PropertyType
Battery replacement canceled - battery parameters are not
reset.
AlarmBatteryChange
Finished
Boolean
PropertyType
Battery replacement finished - counters have been reset.
AlarmBatteryChange
Started
Boolean
PropertyType
Battery replacement started by user
AlarmBattery
CommunicationFault
Boolean
PropertyType
Communication with formerly known battery is no longer
possible - check communication
AlarmBatteryDeepDis-
chargedNoCharging
Possible
Boolean
PropertyType
Battery is deep discharged, charging not possible.
AlarmBatteryDefect
Boolean
PropertyType
Battery defective - check fuse and battery voltages.
AlarmBatteryEndOf
LifetimePrewarning
Boolean
PropertyType
Calculated battery service life almost reached. Only restrict-
ed buffer readiness probable.
AlarmBattery
EndOfLifetimeWarning
Boolean
PropertyType
Calculated battery service life reached, battery replacement
recommended.
AlarmBattery
TemperatureHigh
Boolean
PropertyType
Battery temperature too high - battery life will be shortened
AlarmBattery
TemperatureLow
Boolean
PropertyType
Battery temperature too low - reduced output current
AlarmFuseBroken
Boolean
PropertyType
Fuse is defective.
AlarmIncompatible
ModuleDetected
Boolean
PropertyType
Incompatible battery module detected.
Содержание 6EP4131-0GB00-0AY0
Страница 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 186: ...Troubleshooting 4 1 Hardware fault SITOP UPS1600 BAT1600 UPS1100 186 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 252: ...Technical data 8 8 Dimension drawing SITOP UPS1600 BAT1600 UPS1100 252 Equipment Manual 07 2021 A5E37775406 11 76 ...
Страница 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...