Technical specifications
6.4 Derating and temperature compensation
3VA molded case circuit breakers
494
Manual, 04/2015, A5E03603177010-02
Example 2: Calculation of the tripping time
Starting point:
Based on the example above, the tripping time for an overcurrent I
O
= 360 A will now be
calculated.
To compensate for the ambient temperature of 60 °C, rather than 50 °C, the thermal trip unit
has been set I
r(60 °C)
= 95 A for a system current I = 90 A.
The first step is to calculate the ratio between the overcurrent and the system current:
I
o
/I = 360 A / 90 A = 4
Using this value, it is now possible to read the tripping time from the characteristics chart:
①
Tripping time (schematic representation)
Содержание 3VA1 100 A
Страница 1: ......
Страница 2: ......
Страница 71: ...Description 2 6 Protection system 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 71 ...
Страница 94: ...Description 2 8 Electronic trip unit 3VA molded case circuit breakers 94 Manual 04 2015 A5E03603177010 02 ...
Страница 149: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 149 ...
Страница 163: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 163 ...
Страница 354: ...Accessories 4 8 Residual current devices 3VA molded case circuit breakers 354 Manual 04 2015 A5E03603177010 02 ...
Страница 392: ...Accessories 4 10 EFB300 external function box 3VA molded case circuit breakers 392 Manual 04 2015 A5E03603177010 02 ...
Страница 418: ...Accessories 4 14 DIN rail adapter 3VA molded case circuit breakers 418 Manual 04 2015 A5E03603177010 02 ...
Страница 514: ...List of abbreviations C 1 Table of abbreviations 3VA molded case circuit breakers 514 Manual 04 2015 A5E03603177010 02 ...
Страница 518: ...Conversion tables 3VA molded case circuit breakers 518 Manual 04 2015 A5E03603177010 02 ...
Страница 531: ...Index 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 531 ...
Страница 532: ......