Accessories
4.11 Test devices
3VA molded case circuit breakers
406
Manual, 04/2015, A5E03603177010-02
Carry out a meter test
The purpose of the meter test is to determine whether the ETU is measuring and displaying
current correctly. A test current of 0.4 x I
rated
is fed into the ETU. The current value measured
by the ETU is then checked to confirm that it matches the test current.
Note
The molded case circuit breaker does not need to be switched to position "ON" for this test.
Execute the test
1.
Connect the TD500 test device to the 3VA2 molded case circuit breaker.
2.
Press the pushbutton labeled <METER>
①
.
The LED in the <METER> pushbutton begins to flash. The test takes approximately 30
seconds.
3.
Wait until the LED in the pushbutton <METER> changes from flashing to steady
illumination.
The test is completed.
4.
Evaluate the test result by the status of the LED labeled "RESULT":
LED "RESULT" is illuminated steadily in green: The test was successful.
LED "RESULT" flashes red: The test was unsuccessful and must be repeated. If the test
fails again, contact Technical Support (Page 12) .
5.
Press the pushbutton <METER> again in order to confirm the test result and restore the
TD500 to its initial state.
Содержание 3VA1 100 A
Страница 1: ......
Страница 2: ......
Страница 71: ...Description 2 6 Protection system 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 71 ...
Страница 94: ...Description 2 8 Electronic trip unit 3VA molded case circuit breakers 94 Manual 04 2015 A5E03603177010 02 ...
Страница 149: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 149 ...
Страница 163: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 163 ...
Страница 354: ...Accessories 4 8 Residual current devices 3VA molded case circuit breakers 354 Manual 04 2015 A5E03603177010 02 ...
Страница 392: ...Accessories 4 10 EFB300 external function box 3VA molded case circuit breakers 392 Manual 04 2015 A5E03603177010 02 ...
Страница 418: ...Accessories 4 14 DIN rail adapter 3VA molded case circuit breakers 418 Manual 04 2015 A5E03603177010 02 ...
Страница 514: ...List of abbreviations C 1 Table of abbreviations 3VA molded case circuit breakers 514 Manual 04 2015 A5E03603177010 02 ...
Страница 518: ...Conversion tables 3VA molded case circuit breakers 518 Manual 04 2015 A5E03603177010 02 ...
Страница 531: ...Index 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 531 ...
Страница 532: ......