Accessories
4.8 Residual current devices
3VA molded case circuit breakers
Manual, 04/2015, A5E03603177010-02
293
4.8
Residual current devices
Residual current devices afford fault protection (formerly referred to as: protection in case of
indirect contact) and supplementary protection (formerly referred to as: protection in case of
direct contact) in low-voltage systems. In the event of a basic insulation failure or direct
contact with live components, they provide some degree of protection to persons, material
assets and livestock against harm.
Operating principle of a residual current device
In fault-free electrical installation, the vector sum of the load currents of all connected
conductors equals zero. A residual current occurring in the protected circuit as the result of
an insulation fault, for example, induces a voltage in the secondary winding of a summation
current transformer. The evaluation electronics system monitors the induced voltage and
transmits a trip command to the RCD trip unit if the trip criterion is fulfilled. The molded case
circuit breaker with residual current protection combination is designed to ensure that the
molded case circuit breaker contacts open if the residual current exceeds a preset value.
4.8.1
Portfolio
The new portfolio of residual current devices includes three different RCD designs so that an
optimum solution is available for every conceivable type of application:
●
Side mounted
●
Loadside
●
Modular
Since all residual current devices can be set to between 0.03 A and maximum 5 A or 30 A,
they are suitable for use in the following applications:
●
Personnel protection: I
Δn
≤ 30
mA with instantaneous tripping
Note
In order to protect personnel, it is necessary to seal the transparent protective cover so
that the 30 mA setting range cannot be changed.
●
Fire protection: I
Δn
≤ 300
mA
●
Protection in the case of indirect contact
●
Ground-fault protection
Содержание 3VA1 100 A
Страница 1: ......
Страница 2: ......
Страница 71: ...Description 2 6 Protection system 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 71 ...
Страница 94: ...Description 2 8 Electronic trip unit 3VA molded case circuit breakers 94 Manual 04 2015 A5E03603177010 02 ...
Страница 149: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 149 ...
Страница 163: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 163 ...
Страница 354: ...Accessories 4 8 Residual current devices 3VA molded case circuit breakers 354 Manual 04 2015 A5E03603177010 02 ...
Страница 392: ...Accessories 4 10 EFB300 external function box 3VA molded case circuit breakers 392 Manual 04 2015 A5E03603177010 02 ...
Страница 418: ...Accessories 4 14 DIN rail adapter 3VA molded case circuit breakers 418 Manual 04 2015 A5E03603177010 02 ...
Страница 514: ...List of abbreviations C 1 Table of abbreviations 3VA molded case circuit breakers 514 Manual 04 2015 A5E03603177010 02 ...
Страница 518: ...Conversion tables 3VA molded case circuit breakers 518 Manual 04 2015 A5E03603177010 02 ...
Страница 531: ...Index 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 531 ...
Страница 532: ......