Accessories
4.8 Residual current devices
3VA molded case circuit breakers
Manual, 04/2015, A5E03603177010-02
347
Installation
Installation
Regardless of the type of connection system installed on the 3VA2 molded case circuit
breaker, the RCD820 is mounted underneath the electronic trip unit of the circuit breaker.
1.
Dismantle the loadside connection components of the molded case circuit breaker and
install the supplied connection components for the residual current device.
2.
Insert the residual current device into the T slots of the molded case circuit breaker.
3.
Push the residual current device backwards until its rear panel is flush with the rear panel
of the molded case circuit breaker.
4.
Screw the molded case circuit breaker to the residual current device. Special connecting
screws are provided on the line side of the residual current device for this purpose.
5.
Place a contact hazard protective cover over the circuit breaker/RCD assembly.
6.
Reinstall the loadside connection components of the molded case circuit breaker at the
outgoing feeder end of the residual current device.
7.
Attach the assembly to a mounting plate using the fastening screws.
Note
Since the outgoing feeder end of the residual current device has exactly the same
connection contours as the 3VA2 molded case circuit breaker, all connection accessories
such as phase barriers, terminal covers, etc. can also be mounted on the residual current
device.
Содержание 3VA1 100 A
Страница 1: ......
Страница 2: ......
Страница 71: ...Description 2 6 Protection system 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 71 ...
Страница 94: ...Description 2 8 Electronic trip unit 3VA molded case circuit breakers 94 Manual 04 2015 A5E03603177010 02 ...
Страница 149: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 149 ...
Страница 163: ...Accessories 4 2 Internal accessories 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 163 ...
Страница 354: ...Accessories 4 8 Residual current devices 3VA molded case circuit breakers 354 Manual 04 2015 A5E03603177010 02 ...
Страница 392: ...Accessories 4 10 EFB300 external function box 3VA molded case circuit breakers 392 Manual 04 2015 A5E03603177010 02 ...
Страница 418: ...Accessories 4 14 DIN rail adapter 3VA molded case circuit breakers 418 Manual 04 2015 A5E03603177010 02 ...
Страница 514: ...List of abbreviations C 1 Table of abbreviations 3VA molded case circuit breakers 514 Manual 04 2015 A5E03603177010 02 ...
Страница 518: ...Conversion tables 3VA molded case circuit breakers 518 Manual 04 2015 A5E03603177010 02 ...
Страница 531: ...Index 3VA molded case circuit breakers Manual 04 2015 A5E03603177010 02 531 ...
Страница 532: ......