background image

2

#61-152
#61-153

SureTest

®

Model ST 1D Instructions

Introduction

The SureTest

®

family of circuit analyzers identify

problems common to electrical circuits quickly,
easily and accurately.  They have a patented
voltage drop test, which applies a full 15 ampere
load without causing interruption to equipment
on the circuit.

Product Features

• Identifies and Locates

Loose Wire Connections
Bad Splices/Receptacles
High Resistance Grounds
False (Bootleg) Grounds
Shared Neutrals

• Verifies

Proper Wiring in 3-Wire Receptacles
Proper GFCI Operation
Dedicated Circuit Presence
Isolated Ground Presence (with the 61-176 Isolated Ground Adapter)

• Measures 

Line Voltage 
Ground Impedance 
% Voltage Drop by Conducting an Actual Full 15 Amp Load Test 
% Voltage Drop by Simulating a 20 Amp Load Test
GFCI Trip Time
Neutral-to-Ground Voltage
Estimated Load on Circuit 

General Operation

The SureTest

®

Model ST-1D Circuit Analyzer takes only seconds to test each

outlet and circuit under a full load.  The ST-1D indicates proper wiring, volt-
age drop and line voltage in an easy pass/fail format.  A simple program-
ming menu gives access to measurements of line voltage, voltage drop at a
full 15 amperes and 20 amperes, ground-to-neutral voltage, estimated load
on the circuit and ground impedance.  The ground fault circuit interrupter
(GFCI) test is performed separately and will disrupt the electrical supply if a
functional GFCI is present.

Any discrepancies from a normal reading indicates that a problem
has been detected in the circuit.  

For use in 3-prong (grounded) outlets, inset the ST-1D into the receptacle
with the ground pin extended.  For use in 2-prong (non-grounded) outlets,
leave the ground pin retracted.  Non-grounded (2-prong) outlets will be
tested for voltage drop and line voltage only.  

WARNING

Do not use on outputs from UPS systems, light dimmers or square
wave generating equipment.

Insert the unit in the receptacle, observe test results, remove and reinsert the
unit while pressing the test button to perform the ground impedance test,
and then move on to the next receptacle.    Allow at least 20 seconds
between insertions.  Repeatedly inserting the SureTest into a receptacle will
exceed its ability to dissipate heat within the unit, resulting in fluctuating
readings or damage to the unit.

False Ground Indication

Sometimes 2-wire receptacles are replaced with 3-wire receptacles to
accommodate 3-wire plugs.  A short placed between ground and neutral on
the back of the receptacle will test and appear to be a normal 3-wire circuit.
Common receptacle testers will test this configuration as a normal 3-wire
outlet.

Display of "FG" on the LED display on power-up indicates a suspected false
ground.  False ground is defined as a short between the ground and neutral
wires very close to the receptacle.  A false ground may also be indicated if
the receptacle is within 15 feet of the neutral-ground bonding point at the
panel, or if conduit is being used as the ground conductor. 

Содержание ST 1D

Страница 1: ...if a functional GFCI is present Any discrepancies from a normal reading indicates that a problem has been detected in the circuit For use in 3 prong grounded outlets inset the ST 1D into the receptac...

Страница 2: ...performed immediately upon insertion of the SureTest into the receptacle Wiring Verification The ST 1D checks receptacle wiring for the following conditions Correct wiring no ground polarity reversed...

Страница 3: ...for 1 second to move through the menu to the next test 1 Insert the ST 1D into the receptacle 2 The LED display will show L n to indicate self calibration of the unit 3 The LED display will show 1 to...

Страница 4: ...isplay will show L G to indicate the ground impedance test 4 The LED display will show 6 to indicate that the measurement is being taken 5 Ground impedance is measured and displayed The ground impedan...

Страница 5: ...nd lead on the adapter to a ground such as a metal water or gas pipe prior to GFCI testing 61 176 Isolated Ground Adapter This adapter allows the operator to verify that a receptacle is completely iso...

Страница 6: ...rst receptacle or at the panel If all branches are in high resistance the problem may be in the circuit from the meter or from the transformer to the service entrance Using the SureTest will help iden...

Страница 7: ...Distortion to 31st Harmonic Additional Features 220 VAC Operation For use with 61 181 500AAC Adaptor Included with 61 181 500AAC Adaptor Event recording SureTest Circuit Harmonics Analyzers 61 150 ST...

Страница 8: ...r or replacement no warranty of mer chantability fitness for a particular purpose or consequential damages IDEAL INDUSTRIES INC Sycamore IL 60178 U S A 800 435 0705 Customer Assistance www idealindust...

Отзывы: