SureTest

®

 

Circuit Analyzer

Wiring Indicators

V
o

l
t

D

r
o
p

L

n

V

o

l

t

A

D VA N C

E

DIS

PLAY

4

Specifications

Case Construction:

GE Cycolac molded plastic

Operating Range:

108 to 132 Volts (61-152)
207 to 253 v. (61-153)

Power Consumption:

1 Watt contin; 1800 W peak

Wiring Indications:

Pass/Fail format.

Digital Display:

Seven segment L.E.D., .3”

Operating Temp.:

0 C to 50 C

Storage Temp.:

-20 C to +65 C

Dimensions:

17.78 x 7.62 x 3.81 cm

Weight:

200 grams (7 ounces)

Accuracy

Line Voltage:

±2.5% full scale ±1 digit

Voltage Drop:

±2.5% full scale ±1 digit

Ground-to-Neutral Voltage:

±2.5% full scale ±1 digit

Est. Load on Circuit:

±10% full scale ±1 digit

Ground Impedance:

±2.5% full scale ±1 digit (0-1 Ohm)
±5.0% full scale ±1 digit (1-2 Ohm)

GFCI Trip Time:

±2.5” full scale ±1 digit

Front Panel Indicators

Test Procedures

Pass/Fail Indication

The ST-1D checks receptacles for proper wiring, and give a pass/fail indica-
tion of voltage drop and line voltage.  These tests are performed immediately
upon insertion of the SureTest into the receptacle.

Wiring Verification

The ST-1D checks receptacle wiring for the following conditions:

Correct wiring, no ground, polarity reversed, no hot, or no neutral or hot and
ground reversed.  These conditions are indicated on the wiring indicators. 

Insert the ST-1D into the receptacle for indication of the wiring condition.

WARNING

An indication of “No Ground” on the wiring indicators indicates a
safety hazard is present.  Defective grounds must be repaired prior to
the GFCI test.

The ST-1D will not indicate a reversal of the ground and neutral 
connections, detect two hot connections, or indicate simultaneous
defects.

Wiring Indicators 
Ground Impedance Indicators
Ground-to-Neutral Indicators
G.F.C.I. Test Button
LED Display

1

2

3

4

5

1

2

3

4

5

1 = Line Voltage
2 = % Voltage Drop 15 AMP
3 = % Voltage Drop 20 AMP
4 = Highest Voltage Gnd./Neutral
5 = Load on line 

±

 10%

6 = Ground Impedance in Ohms
(Hold button insert Sure Test)

GFCI Test.  Hold Button 3 Sec.

61-152

ST-1D

FG = False Ground

WIRING INDICATIONS

NORMAL

NO GROUND
POLARITY REVERSED
NO HOT
NO NEUTRAL or
HOT/GROUND REVERSED

ON

OFF

3

Содержание ST 1D

Страница 1: ...if a functional GFCI is present Any discrepancies from a normal reading indicates that a problem has been detected in the circuit For use in 3 prong grounded outlets inset the ST 1D into the receptac...

Страница 2: ...performed immediately upon insertion of the SureTest into the receptacle Wiring Verification The ST 1D checks receptacle wiring for the following conditions Correct wiring no ground polarity reversed...

Страница 3: ...for 1 second to move through the menu to the next test 1 Insert the ST 1D into the receptacle 2 The LED display will show L n to indicate self calibration of the unit 3 The LED display will show 1 to...

Страница 4: ...isplay will show L G to indicate the ground impedance test 4 The LED display will show 6 to indicate that the measurement is being taken 5 Ground impedance is measured and displayed The ground impedan...

Страница 5: ...nd lead on the adapter to a ground such as a metal water or gas pipe prior to GFCI testing 61 176 Isolated Ground Adapter This adapter allows the operator to verify that a receptacle is completely iso...

Страница 6: ...rst receptacle or at the panel If all branches are in high resistance the problem may be in the circuit from the meter or from the transformer to the service entrance Using the SureTest will help iden...

Страница 7: ...Distortion to 31st Harmonic Additional Features 220 VAC Operation For use with 61 181 500AAC Adaptor Included with 61 181 500AAC Adaptor Event recording SureTest Circuit Harmonics Analyzers 61 150 ST...

Страница 8: ...r or replacement no warranty of mer chantability fitness for a particular purpose or consequential damages IDEAL INDUSTRIES INC Sycamore IL 60178 U S A 800 435 0705 Customer Assistance www idealindust...

Отзывы: