background image

12

11

#61-179  Carrying Case

The ST-1 is supplied with a lightweight carrying case to protect the units
and store the instruction sheet and accessories.  Replacement cases can be
purchased from your authorized IDEAL distributor.

Troubleshooting

Locating Loose (High Resistance) Connections and Splices

Loose connections, splices and bad connections can be isolated by using
the SureTest to test receptacles in sequence along the branch circuit.

For example if the voltage drop at receptacle 5 is unacceptable, checking the
other receptacles in the branch can help isolate the problem.  If receptacles
1 through 4 and 6 through 8 check out OK, than further investigation should
take place at the connection to receptacle 5.  The additional resistance could
be due to a loose connection/splice.  If receptacles 6 through 8 are also
unacceptable, chances are that the problem is in either the hot or neutral
conductor in the wall between receptacles 4 and 5.

If all of the branch receptacles have unacceptable voltage drops, the problem
is most likely in the circuit between the panel and the first receptacle or at
the panel.  If all branches are in high resistance, the problem may be in the
circuit from the meter, or from the transformer to the service entrance.

Using the SureTest will help identify problem areas for further investigation
of the receptacles and/or branch circuit.

Troubleshooting Tips

Problem

Possible Causes/Solutions

High/Low Line Voltage

• Too much load on branch ñ also causing

excessive voltage drop

• Poor connection at receptacle
• Supply voltage too high/low
• Clean and tighten receptacle connections
• Consult power company

High Voltage Drop

• Too much load on branch

(5% recommended by NEC)

• Too many outlets on branch
• Diameter of wire too small
• Check and tighten connection at 

receptacle

• Clean any corroded wires
• Replace outlet, switch
• Replace circuit breaker

High Ground-to-Neutral 

• Current flowing in the neutral conductor

Voltage (Greater than 

• Locate/repair source

2 Volts)

• Install surge suppression

High Ground Impedance 

• Loose ground connection

(Greater than 1 Ohm)

• Check and tighten ground connections
• Clean any corroded wires

Failure of GFCI Test

• GFCI may be installed incorrectly

(GFCI will not trip)

• GFCI may be defective
• Check for proper connections
• Replace outlet

WARNING

Maintenance on electrical wiring should only be performed by quali-
tied personnel.

Содержание ST 1D

Страница 1: ...if a functional GFCI is present Any discrepancies from a normal reading indicates that a problem has been detected in the circuit For use in 3 prong grounded outlets inset the ST 1D into the receptac...

Страница 2: ...performed immediately upon insertion of the SureTest into the receptacle Wiring Verification The ST 1D checks receptacle wiring for the following conditions Correct wiring no ground polarity reversed...

Страница 3: ...for 1 second to move through the menu to the next test 1 Insert the ST 1D into the receptacle 2 The LED display will show L n to indicate self calibration of the unit 3 The LED display will show 1 to...

Страница 4: ...isplay will show L G to indicate the ground impedance test 4 The LED display will show 6 to indicate that the measurement is being taken 5 Ground impedance is measured and displayed The ground impedan...

Страница 5: ...nd lead on the adapter to a ground such as a metal water or gas pipe prior to GFCI testing 61 176 Isolated Ground Adapter This adapter allows the operator to verify that a receptacle is completely iso...

Страница 6: ...rst receptacle or at the panel If all branches are in high resistance the problem may be in the circuit from the meter or from the transformer to the service entrance Using the SureTest will help iden...

Страница 7: ...Distortion to 31st Harmonic Additional Features 220 VAC Operation For use with 61 181 500AAC Adaptor Included with 61 181 500AAC Adaptor Event recording SureTest Circuit Harmonics Analyzers 61 150 ST...

Страница 8: ...r or replacement no warranty of mer chantability fitness for a particular purpose or consequential damages IDEAL INDUSTRIES INC Sycamore IL 60178 U S A 800 435 0705 Customer Assistance www idealindust...

Отзывы: