background image

Installation Instructions

Item:

Solid State Molded Case Circuit
Breaker Sentron Series Sensitrip III

Devices:

I-T-E

®

MD Frame Types SMD6,

SHMD6, and SCMD6. ND Frame Types
SND6, SHND6, and SCND6.

Page

1 of 6

Hazardous Voltage.
Will cause death or severe
injury.

Turn off and lock out all power supplying this
device before removing cover(s) or device
and while cover(s) are removed.

Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750, TA3N8750,
OR TA4N8500 ARE USED.

Replace all covers and shields before power
supplying this device is turned on.

NOTE:

 This instruction outlines the recommended

installation procedure.

Introduction

The MD and ND Frame circuit breaker line includes
SMD6, SHMD6, SCMD6, SND6, SHND6 and
SCND6 circuit breaker types. These devices are
rated for operating voltages up to 600 VAC, 50/60 Hz.

Installation

The MD and ND Frame circuit breaker devices are
for use in individual enclosures, panelboards or
other approved equipment.
The installation procedure consists of inspecting,
attaching required accessories, mounting the de-
vice and connecting and torquing the line and load
wire connectors.
Mounted hardware and unmounted wire connec-
tors (where required) are available as separate cata-
log items.

Circuit Breaker Preparation

A. Before installing or servicing the breaker, turn

off and lock out all power to prevent incidental or
accidental contact.

B. Make sure that the device is suitable for the in-

stallation by comparing nameplate ratings with
system requirements. Inspect the device for com-
pleteness and check for any damage before
mounting.

Fig. 1

NOTE:

Accessory installation should be complete
before the circuit breaker is mounted and
connected. (See installation instructions
supplied with the Accessory before pro-
ceeding.)

C. Depress the red trip button (See Fig. 4) or turn

the breaker off before installation.

D. To  mount the device, perform the following steps:

1.  For enclosures, panelboards and switch

boards manufactured by Siemens Energy &
Automation, Inc., follow instructions provided
with the equipment.

SAFETY INSTRUCTIONS

Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.

Released Production, B v1, Dec 18, 1998

I-T-E

®

 MD Frame Types SMD6,

SHMD6, and SCMD6(-A). ND Frame
Types SND6, SHND6, and SCND6(-A).

The MD and ND Frame circuit breaker line includes
SMD6, SHMD6, SCMD6(-A), SND6, SHND6 and
SCND6(-A) circuit breaker types. These devices are
rated for operating voltages up to 600 VAC, 50/60 Hz.

Released Production, C v1, Apr 18, 2011

Содержание SMD6

Страница 1: ...nectors Mounted hardware and unmounted wire connec tors where required are available as separate cata log items Circuit Breaker Preparation A Before installing or servicing the breaker turn off and lock out all power to prevent incidental or accidental contact B Make sure that the device is suitable for the in stallation by comparing nameplate ratings with system requirements Inspect the device fo...

Страница 2: ...n securely 5 Connect the line and load terminals and torque using the values shown on the circuit breaker nameplate 6 Connect all accessory terminals if present 7 Check all mounting hardware for secureness Check wire connectors for correct torque requirements Manual Operation Manual operation of the device is controlled by the circuit breaker handle and the PUSH TO TRIP button The device handle ha...

Страница 3: ...rame devices are designed to provide years of maintenance free service Sensitrip III Solid State Molded Case circuit breakers may be tested for electronic functionality by the use of TS 31 test set available from local Siemens sales offices Maintenance Experience has shown that properly applied molded case circuit breakers normally do not require main tenance However some industrial users may choo...

Страница 4: ...es the continuous amps setting The dia gram below illustrates the possible settings for this switch Short Time Pickup xIr Long Time Delay 6xIr The adjustable long time delay switch allows for se lection of long time delays based on I2 t curves at six time the continuous amps setting Ir The dia gram below illustrates the possible settings for this switch Continuous Amps Ir In Long Time Delay Secs 6...

Страница 5: ...fault option has two modes of opera tion The mode is set by a switch on the bottom of the trip unit with the settings identified as RESIDUAL and GROUND RETURN See Fig 4 for switch lo cation RESIDUAL MODE OUTGOING CIRCUIT METHOD This is the standard position that the breaker is set to when shipped from the factory With the switch in this position the circuit breaker may be used on 3 phase 3 wire or...

Страница 6: ... sensors listed below must be used for these applications The sensor catalog number must be matched to the cir cuit breaker Maximum Continuous Current rating In as shown in the table Please note that sen sors used with other breaker types cannot be used with the SMD SND circuit breakers Installation in structions are included with the sensors Transformer Circuit Transformer Catalog No Breaker Rati...

Отзывы: