background image

Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.

Installation Instructions

Hazardous Voltage.
Will cause death or severe
injury.

Turn off and lock out all power supplying this
device before removing cover(s) or device
and while cover(s) are removed.

Wire connector shield no. NDTS must be
installed when wire connectors TA2K8750,
TA3P8750, TA4P8500, TA2N8750,
TA3N8750, OR TA4N8500 ARE USED.

Replace all covers and shields before power
supplying this device is turned on.

Page 

4 of 6

Continuous Current Switch Ir=%In

Adjustments made to this switch can change the
continuous amps rating of the breaker to 20, 30,
40, 50, 60, 70, 80, 90 or 100% of the maximum
continuous amps rating (In) of the circuit breaker.

The diagram below shows the settings possible on
this switch.

Short Time  Delay  (optional)

The adjustable short time delay switch allows for
selection from two ranges of short time delays. The
first range of settings enable the breaker to be set
for fixed time delays of .05, .1, .2, .3, or .5 seconds.
The second range of settings enable the breaker
to be set for short time delays based on I

2

t curves

at six times the continuous amps setting. The dia-
gram below illustrates the possible settings for this
switch.

Short Time
Pickup

xIr

Long Time Delay @ 6xIr

The adjustable long time delay switch allows for se-
lection of long time delays based on I

2

t curves at

six time the continuous amps setting (Ir). The dia-

gram below illustrates the possible settings for this
switch.

Continuous Amps

Ir = %In

Long Time Delay

Secs @
6xIr

Short Time  Pickup

xIr (optional)

Circuit breakers with the letters “NT” in the catalog
number have adjustments to set the Short Time
Pickup and the Short Time Delay.

The adjustable short time pickup switch allows for
selection of short time pickup in a range from 1.5
to 10 times the setting of the Adjustable Continu-
ous Amps Switch. The OFF position disables the
function. The diagram below illustrates the possible
settings for this switch.

Short Time Delay

I

2

t @

6xIr
Secs.

ELECTRONIC OPERATION

The setting dials on the face of the electonic trip
unit are rotary switches that must be properly set
to mechanical detent (click stop) positions.  An
improper switch setting will cause the trip unit to
default (as a fail safe condition) to the lowest
permissive setting and, consequently, may result
in unintentional or nuisance tripping.

8

Released Production, B v1, Dec 18, 1998

Released Production, C v1, Apr 18, 2011

Содержание SMD6

Страница 1: ...nectors Mounted hardware and unmounted wire connec tors where required are available as separate cata log items Circuit Breaker Preparation A Before installing or servicing the breaker turn off and lock out all power to prevent incidental or accidental contact B Make sure that the device is suitable for the in stallation by comparing nameplate ratings with system requirements Inspect the device fo...

Страница 2: ...n securely 5 Connect the line and load terminals and torque using the values shown on the circuit breaker nameplate 6 Connect all accessory terminals if present 7 Check all mounting hardware for secureness Check wire connectors for correct torque requirements Manual Operation Manual operation of the device is controlled by the circuit breaker handle and the PUSH TO TRIP button The device handle ha...

Страница 3: ...rame devices are designed to provide years of maintenance free service Sensitrip III Solid State Molded Case circuit breakers may be tested for electronic functionality by the use of TS 31 test set available from local Siemens sales offices Maintenance Experience has shown that properly applied molded case circuit breakers normally do not require main tenance However some industrial users may choo...

Страница 4: ...es the continuous amps setting The dia gram below illustrates the possible settings for this switch Short Time Pickup xIr Long Time Delay 6xIr The adjustable long time delay switch allows for se lection of long time delays based on I2 t curves at six time the continuous amps setting Ir The dia gram below illustrates the possible settings for this switch Continuous Amps Ir In Long Time Delay Secs 6...

Страница 5: ...fault option has two modes of opera tion The mode is set by a switch on the bottom of the trip unit with the settings identified as RESIDUAL and GROUND RETURN See Fig 4 for switch lo cation RESIDUAL MODE OUTGOING CIRCUIT METHOD This is the standard position that the breaker is set to when shipped from the factory With the switch in this position the circuit breaker may be used on 3 phase 3 wire or...

Страница 6: ... sensors listed below must be used for these applications The sensor catalog number must be matched to the cir cuit breaker Maximum Continuous Current rating In as shown in the table Please note that sen sors used with other breaker types cannot be used with the SMD SND circuit breakers Installation in structions are included with the sensors Transformer Circuit Transformer Catalog No Breaker Rati...

Отзывы: