WARNING

In order to test GFCI’s in a 2-wire system (no ground wire), the #61-175
ground continuity adapter must be used.  Connect the ground lead on
the adapter to a ground, such as a metal water or gas pipe.

Optional Accessories

#61-175  Ground Continuity Adapter

This adapter allows the operator to verify that a cabinet or equipment chas-
sis has been properly connected to the power system ground.  Plugging into
the #61-175 adapter will isolate the SureTest from the power source ground.
The Wiring Indicators of the unit will display a No Ground condition.  If the
equipment is properly grounded, then touching the alligator clip from the
ground continuity adapter to the cabinet or equipment chassis should return
the circuit to a Normal condition.  

WARNING

This is a static test and will not confirm the current carrying capacity
of the ground.

With the ST-1D, this adapter can be used to check the ground impedance of
a cabinet or equipment chasis.  See the Ground Impedance Measurement
section for test instructions.

This adapter can also be used to test GFCI receptacles on 2-wire circuits.
Connect the ground lead on the adapter to a ground, such as a metal water
or gas pipe, prior to GFCI testing. 

#61-176  Isolated Ground Adapter

This adapter allows the operator to verify that a receptacle is completely iso-
lated from the other grounds between the receptacle and the entry panel.  

WARNING

The receptacle should be tested for proper grounding prior to testing
for ground insulation.

Test the ground impedance of the receptacle and make a note of the results.
See the section on ground impedance testing for details.  Remove the
SureTest from the receptacle and plug it into the #61-176 adapter.  Clip the
ground wire to the metal outlet, center receptacle screw, or the metal outlet
box.  Press the display advance button, and re-insert the ST-1D into the
receptacle.  Make a note of the result.

If the two resistance readings are the same, then the receptacle is not isolat-
ed.  If the receptacle is isolated, the reading with the #61-176 will be lower.
A reading of half when the adapter is used is common, because a parallel
ground path has been introduced by attaching the ground wire to the
grounding point of the receptacle.

#61-177  Extension Cord

The ST-1 is supplied with an extension cord to make testing easier on hard-
to-reach outlets.  Replacement extension cords can be purchased from your
authorized IDEAL distributor.

Содержание ST 1D

Страница 1: ...if a functional GFCI is present Any discrepancies from a normal reading indicates that a problem has been detected in the circuit For use in 3 prong grounded outlets inset the ST 1D into the receptac...

Страница 2: ...performed immediately upon insertion of the SureTest into the receptacle Wiring Verification The ST 1D checks receptacle wiring for the following conditions Correct wiring no ground polarity reversed...

Страница 3: ...for 1 second to move through the menu to the next test 1 Insert the ST 1D into the receptacle 2 The LED display will show L n to indicate self calibration of the unit 3 The LED display will show 1 to...

Страница 4: ...isplay will show L G to indicate the ground impedance test 4 The LED display will show 6 to indicate that the measurement is being taken 5 Ground impedance is measured and displayed The ground impedan...

Страница 5: ...nd lead on the adapter to a ground such as a metal water or gas pipe prior to GFCI testing 61 176 Isolated Ground Adapter This adapter allows the operator to verify that a receptacle is completely iso...

Страница 6: ...rst receptacle or at the panel If all branches are in high resistance the problem may be in the circuit from the meter or from the transformer to the service entrance Using the SureTest will help iden...

Страница 7: ...Distortion to 31st Harmonic Additional Features 220 VAC Operation For use with 61 181 500AAC Adaptor Included with 61 181 500AAC Adaptor Event recording SureTest Circuit Harmonics Analyzers 61 150 ST...

Страница 8: ...r or replacement no warranty of mer chantability fitness for a particular purpose or consequential damages IDEAL INDUSTRIES INC Sycamore IL 60178 U S A 800 435 0705 Customer Assistance www idealindust...

Отзывы: